Dixell/Copeland AL31 Error Code
. the start-up of the condenser pump. It turns to manual if If CO26=0: Flashing
Source: IC100CX_QRG_GB.pdf
What does Dixell/Copeland AL31 mean?
The AL31 alarm on the Dixell IC100CX iChill controller indicates a condenser pump flow or start-up alarm. It activates at the start-up of the condenser pump when the condenser water flow switch input does not close within the expected time, or transitions to a manual reset state if the no-flow condition persists. The alarm icon flashes on the display until the condition is resolved and the alarm is manually reset.
Symptoms
- AL31 displayed on the IC100CX with flashing alarm icon.
- Condenser pump may be running but flow switch input remains inactive.
- Alarm relay activates.
- System may delay or prevent compressor start to protect the condenser.
Common causes
- Condenser water pump failed to develop adequate flow at start-up.
- Condenser water flow switch requires longer time to close than the controller allows.
- Air-locked condenser circuit preventing pump from generating flow.
- Flow switch misadjusted — set threshold too high for installed pump flow rate.
- Condenser water pump rotation reversed — wired incorrectly on three-phase supply.
Ask the AskWhiz AI about Dixell/Copeland AL31
AskWhiz
online
Diagnostic steps
Confirm condenser pump rotation and flow
Verify the condenser pump is rotating in the correct direction. On three-phase motors, incorrect phase rotation causes reverse rotation and near-zero flow; check rotation by briefly running the pump and observing flow direction.
Test the condenser flow switch response time
Time how long the condenser flow switch takes to close after pump start. If it consistently exceeds the start-up delay, increase the start-up delay parameter to match actual system response.
Purge air from the condenser circuit
Open air vents at high points of the condenser water loop. An air-bound pump cannot develop rated flow; purging air restores normal operation.
Check flow switch calibration
Confirm the flow switch paddle or vane is adjusted correctly for the actual condenser circuit flow rate. An over-sensitive setting will prevent the switch from closing at normal flow.
Manually reset and monitor
After restoring condenser water flow, navigate to AlrM on the IC100CX, select AL31, and press SET to perform the manual reset. Monitor the flow switch input to confirm it stays closed during normal pump operation.
When to call a professional
Call a licensed HVAC/R technician if the condenser pump motor requires mechanical repair or if phase rotation correction requires re-wiring a three-phase supply — electrical work on three-phase circuits must be performed by a licensed electrician in most jurisdictions.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com