Dixell/Copeland AL33 Error Code
2= activated only in h.p. mode 3= activated in chiller and h.p. mode Disable flo
Source: IC100CX-FW1.8-GRU-GB.pdf
What does Dixell/Copeland AL33 mean?
On the Dixell IC100CX iChill controller, AL33 controls whether the condenser water flow switch alarm is suppressed when the condenser water pump is off. Set AL33 to 0 to keep the flow alarm active even when the pump is off. Set AL33 to 1 to disable the flow switch alarm when the condenser pump is not running, preventing nuisance alarms during pump shutdown periods when no water flow is expected.
Symptoms
- Condenser water flow alarm triggers immediately when condenser pump stops (if AL33 = 0 and pump-off is normal).
- No flow alarm generated when pump is off even if flow switch contacts indicate a fault (if AL33 = 1).
- System may lock out from condenser flow alarm during normal pump cycling if AL33 is not set correctly.
Common causes
- AL33 = 0 but system design uses condenser pump cycling — nuisance alarms during pump-off periods.
- AL33 = 1 but a genuine condenser flow loss occurs during pump operation — alarm is masked.
- AL31 (condenser flow switch alarm configuration: chiller only, HP only, or both modes) mismatched with AL33.
Ask the AskWhiz AI about Dixell/Copeland AL33
AskWhiz
online
Diagnostic steps
Determine condenser pump operating mode
Review whether the condenser water pump (CO26 parameter) runs continuously or cycles. If the pump cycles off during normal operation, set AL33 = 1 to suppress flow alarms during off periods.
Verify AL31 configuration
Check AL31 (0 = not used, 1 = chiller mode only, 2 = heat pump mode only, 3 = both modes). Confirm AL31 matches the operating modes where condenser flow protection is required.
Test the condenser flow switch
With the condenser pump running, verify the flow switch closes and AL33 logic allows the alarm to activate if flow is lost. Confirm switch wiring integrity and proper calibration of the flow switch.
Check AL27 and AL28 delay parameters
AL27 is the condenser flow alarm delay (seconds). AL28 is the maximum duration before the alarm becomes manual reset and blocks the pump. Verify these are set appropriately for the system.
Set AL33 correctly and test
Set AL33 = 1 if pump cycling is normal, or AL33 = 0 if continuous pump operation is required and loss of flow must always alarm. Test by temporarily stopping the pump and confirming controller behavior.
When to call a professional
If condenser flow loss alarms are occurring during normal operation and cannot be resolved by parameter adjustment, a licensed HVAC/R technician should inspect the condenser water circuit for blockages, pump issues, or incorrect system balance. Chiller condenser water circuit commissioning is typically a specialist activity.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com, webapps.copeland.com