Dixell/Copeland E01
DLT alarm active Output disabled, alam output activated E02 hours) dLi was detec
Source: XEV02D-GB.pdf
What does Dixell/Copeland E01 mean?
On the Dixell XEV02D digital compressor PWM valve driver, E01 indicates an active DLT (Discharge Line Temperature) alarm. The DLT probe P2 has measured a temperature at or above the dLt setpoint. The module disables its output and activates the alarm relay. The fault resets automatically once P2 drops below dLt minus the dth differential and the compressor head-cooling standby timer (dCt) expires.
Symptoms
- Display shows 'E01'; output TRIAC and compressor relay are disabled.
- Alarm relay and open-collector output activate.
- Buzzer sounds (if enabled via bEn parameter).
- Regulation restarts automatically after temperature drops below reset threshold and dCt timer expires.
Common causes
- Discharge line temperature exceeding the dLt setpoint — most commonly from insufficient refrigerant charge.
- Condenser coil fouled or airflow restricted, causing high condensing temperature.
- DLT probe P2 incorrectly positioned or not making proper thermal contact with the discharge line.
- Faulty or out-of-calibration DLT probe reading higher than actual temperature.
- System operating outside design load conditions, driving discharge temperature above limits.
Diagnostic steps
- 01
Verify DLT probe placement and contact
Confirm that probe P2 is properly clamped to the discharge line, at the recommended location per system design. Poor contact causes false high readings.
- 02
Check refrigerant charge
Connect manifold gauges. Low refrigerant charge is the leading cause of elevated discharge temperatures. Compare suction and discharge pressures to design values for the operating conditions.
- 03
Inspect condenser coil and airflow
Clean condenser coil if dirty. Confirm condenser fan(s) are operating and that no airflow recirculation is occurring. Elevated condensing temperature directly raises discharge temperature.
- 04
Check dLt parameter setting
Verify the dLt setpoint in the XEV02D parameter menu is appropriate for the application refrigerant. An incorrectly low setpoint generates nuisance trips.
- 05
Allow automatic reset
Once root cause is corrected, the E01 alarm resets automatically when temperature falls below (dLt − dth) and the dCt head-cooling timer expires. No manual reset is required for single-event DLT trips.
Keep this fix — get it by email with every Dixell/Copeland error code
A clean printable version of this Dixell/Copeland E01 guide + the full Dixell/Copeland code pack (59 codes), straight to your inbox. Free.
When to call a professional
If discharge temperatures remain elevated after verifying condenser operation, or if a refrigerant charge issue is identified, a licensed refrigeration technician is required for refrigerant system service. Repeated E01 events that escalate to E02 lockout require manual controller reset and an investigation into system-level overload conditions.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Dixell/Copeland error codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
F7(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
F8(AF15) time When theinput is disable: according to the working algorithm. turn o
F1(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
F2AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
F12) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
E2Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
AL11temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
AL10events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
AL06; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
AL07. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
AL24. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com