Dixell/Copeland E05 Error Code
below dSL value more than dEr time) E07 Low temperature alarm active Output disa
Source: XEV02D-GB.pdf
What does Dixell/Copeland E05 mean?
On the Dixell XEV02D, E05 is a missing regulation signal alarm. The analogue control input (0–10 V or 4–20 mA) from the master controller has dropped below the dSL threshold (minimum signal level in percent) for longer than the dEr timer. The module disables its outputs and activates the alarm relay. The alarm resets automatically once the control signal recovers above dSL.
Symptoms
- Display shows 'E05'; TRIAC output, compressor relay, and valve control are disabled.
- Alarm relay activates.
- System stops modulating the digital unloader valve.
- Fault clears automatically when signal exceeds dSL — no manual reset required.
Common causes
- Master controller analogue output failure or wiring break between master and XEV02D.
- Incorrect signal type wired (e.g., 0–10 V connected but XEV02D configured for 4–20 mA).
- Master controller in alarm or off state, dropping its analogue output to zero.
- dSL parameter set too high, causing trips during normal low-load operation.
- Interference or ground loops corrupting the analogue signal below threshold.
Ask the AskWhiz AI about Dixell/Copeland E05
AskWhiz
online
Diagnostic steps
Measure the analogue control signal at XEV02D input terminals
Using a multimeter, verify the voltage (0–10 V) or current (4–20 mA) at XEV02D input terminals. Compare to the expected signal from the master controller at current operating conditions.
Check master controller status
Confirm the master controller is powered, in regulation mode, and actively outputting a control signal. A controller in alarm or standby mode may drop its output to zero, triggering E05.
Inspect analogue signal wiring
Check wiring continuity from master controller analogue output to XEV02D input terminals. Look for loose terminals, damaged cable, or connections crossed with other circuits.
Verify dSL parameter setting
Check parameter dSL in the XEV02D menu. If dSL is set too high (e.g., 20%), low-load operation may legitimately drop below it. Adjust to match the application minimum signal level.
Check Si0 and Si1 input scaling parameters
Verify that Si0 (minimum input %) and Si1 (maximum input %) match the master controller's output range. Incorrect scaling shifts the effective dSL threshold.
When to call a professional
If the master controller itself is faulty and generating an invalid signal, or if the analogue wiring runs are complex, involve a qualified service technician familiar with both the master controller and the XEV02D configuration. Analogue signal calibration and multi-controller integration issues often require systematic bench testing.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com