Dixell/Copeland E12
,E22EMB1 or 2:under speed Regulation stopped, retry function active Regulationst
Source: XWi70K-EN.pdf
What does Dixell/Copeland E12 mean?
The XWi70K controller reports E12 when Embraco variable-speed compressor 1 (EMB1) has fallen below its minimum operating speed threshold. Regulation is stopped and the built-in retry function activates automatically. The same fault on compressor 2 is displayed as E22. This is a serial-bus fault reported directly from the Embraco inverter module over the CAB/EMB serial cable.
Symptoms
- Controller display shows 'E12' or 'E22' for compressor 1 or 2 respectively.
- Compressor output relay de-energizes; cooling regulation stops.
- Alarm output activates and buzzer sounds.
- Retry function cycles the compressor; unit attempts automatic restart.
Common causes
- Low supply voltage causing the inverter to lose speed control.
- Refrigerant charge too low, reducing compressor load and causing speed drop.
- Mechanical restriction in the compressor (seized bearings or locked rotor at low speed).
- Faulty or damaged CAB/EMB serial cable between controller and Embraco inverter.
- Inverter module failure — internal drive fault flagging under-speed to the XWi70K.
Diagnostic steps
- 01
Check supply voltage
Measure AC supply at the unit terminals. Voltage must be within ±10% of rated value. Low voltage is the leading cause of inverter under-speed trips.
- 02
Inspect the CAB/EMB serial cable
Verify cable DD190001 51 (for Embraco models) is fully seated at both the XWi70K serial port and the compressor inverter port. Reseat connectors and inspect for damage or corrosion.
- 03
Check refrigerant charge
Connect manifold gauges and compare suction and discharge pressures to manufacturer spec. An undercharged system reduces motor load and can cause the inverter to detect under-speed.
- 04
Allow automatic retry
The XWi70K retry function will attempt to restart the compressor automatically. Monitor the number of retry attempts; if faults repeat continuously, proceed with further diagnostics.
- 05
Inspect Embraco inverter module
Check the inverter module for fault LEDs or diagnostic codes per the Embraco inverter product manual. A hardware fault in the module requires inverter replacement.
Keep this fix — get it by email with every Dixell/Copeland error code
A clean printable version of this Dixell/Copeland E12 guide + the full Dixell/Copeland code pack (59 codes), straight to your inbox. Free.
When to call a professional
Call a licensed refrigeration technician if the fault recurs after multiple automatic retries, if supply voltage checks out, or if the refrigerant system requires service. Inverter module replacement and refrigerant system work require certified technicians. Repeated under-speed faults that are not cleared by retry indicate a hardware problem beyond field-level reset.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Dixell/Copeland error codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
F7(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
F8(AF15) time When theinput is disable: according to the working algorithm. turn o
F1(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
F2AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
F12) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
E2Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
AL11temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
AL10events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
AL06; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
AL07. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
AL24. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com