Dixell/Copeland F01 Error Code
C_n(0) - 0_n(1)- Fan operating mode C_Y(2) - 0_Y(3) F02 Fan stop temperature 55.
Source: IC70CX-EN.pdf
What does Dixell/Copeland F01 mean?
On the Dixell IC70CX iChill controller, F01 selects the evaporator fan operating mode. Four modes are available: C_n (fan runs with compressor, off during defrost), o_n (fan always on, off during defrost), C_Y (fan runs with compressor, on during defrost), and o_Y (fan always on, including during defrost). The correct mode depends on the application — chiller units typically use C_n or C_Y while some applications require continuous fan operation.
Symptoms
- Fan continues running during defrost when it should be off (F01 = C_Y or o_Y but application requires fans off during defrost).
- Fan stops when compressor stops but application requires continuous air circulation (F01 = C_n but o_n needed).
- Defrost not clearing ice effectively due to fans blowing cold ambient air across the coil (F01 = o_Y on an outdoor unit).
Common causes
- F01 set to incorrect mode during commissioning for the specific application.
- System modification (e.g., change from chilled water to direct expansion) requiring a different fan mode.
- Controller replacement without restoring the original F01 setting from commissioning records.
Ask the AskWhiz AI about Dixell/Copeland F01
AskWhiz
online
Diagnostic steps
Identify required fan operating mode for the application
Review the system design specification or OEM documentation to determine whether fans should run continuously or only with the compressor, and whether they should run during defrost.
Check current F01 setting
Access the F parameter sub-menu on the IC70CX and view the current F01 value: C_n, o_n, C_Y, or o_Y.
Set F01 to the correct mode
Change F01 to match the application. Use C_n for compressor-interlocked fans with defrost shutoff, o_n for continuous fans with defrost shutoff, C_Y for compressor-interlocked fans that run during defrost, or o_Y for always-on fans including during defrost.
Verify F02 fan stop temperature
F02 sets the evaporator temperature below which the fan is switched off. Confirm F02 is correctly set to prevent fan operation when evaporator temperature is too low (typically to protect against icing on evaporator fans).
Test fan behavior across operating modes
Cycle the unit through compressor on, compressor off, and defrost states to confirm the fan behaves correctly in each state per the F01 setting.
When to call a professional
F01 is a commissioning parameter — changes require understanding of the full system design. If the IC70CX is part of a chiller installation and fan mode changes affect system performance or zone temperatures, involve the commissioning engineer or a licensed HVAC/R technician who is familiar with the installation.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com