Dixell/Copeland F07 Error Code
with alarm dF02=1 A13 Compressor 1Running hour> CO14 maintenance warning A14 A15
Source: IC100CX_QRG_GB.pdf
What does Dixell/Copeland F07 mean?
The F07 alarm on the Dixell IC100CX iChill controller is a compressor 1 running hours maintenance warning. When Compressor 1's cumulative operating hours exceed the threshold set in parameter CO14, the controller displays F07 to alert maintenance personnel that scheduled service is due. This is a non-locking warning — the compressor continues to run normally. Additional codes F08 (Compressor 2) and related variants follow the same logic.
Symptoms
- F07 displayed on the IC100CX controller screen as a warning.
- Compressor continues to operate normally — no shutdown occurs.
- Alarm icon may illuminate to draw attention to the maintenance notification.
- Warning persists until the running hours counter is manually reset.
Common causes
- Compressor 1 has accumulated running hours equal to or exceeding the CO14 maintenance interval.
- Maintenance hours counter was not reset after previous scheduled service.
- CO14 parameter set to a very short interval resulting in early notification.
Ask the AskWhiz AI about Dixell/Copeland F07
AskWhiz
online
Diagnostic steps
Perform compressor maintenance
Complete all scheduled maintenance tasks for Compressor 1 per the compressor manufacturer's service manual — typically including oil inspection, belt tension check (if applicable), electrical connection tightening, and vibration check.
Inspect compressor oil and check valves
For compressors with oil sight glasses, verify oil level and condition. Change compressor oil if discolored or acidic. Replace oil filter if fitted.
Check electrical connections
Inspect and torque all compressor power terminal connections. Loose connections cause overheating and contribute to motor failures before the next maintenance interval.
Reset the running hours counter
Access the IC100CX service menu and navigate to the compressor hours counter for Compressor 1. Reset the counter to zero after completing all maintenance tasks.
Verify CO14 maintenance interval
Confirm the CO14 parameter is set to the correct maintenance interval per the compressor manufacturer's recommendation — typically 2,000 to 8,760 hours depending on the compressor model and application.
When to call a professional
Call a licensed refrigeration technician if compressor oil analysis indicates acid or moisture contamination (indicating refrigerant leakage past compressor seals), if compressor electrical insulation testing reveals degraded windings, or if the maintenance reveals abnormal vibration or noise that warrants further compressor assessment.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com