Dixell/Copeland F11
Temperature setpoint to start a combined defrost cycle after -50.0 the DF10 coun
Source: IC100CX-FW1.8-GRU-GB.pdf
What does Dixell/Copeland F11 mean?
On the Dixell IC100CX iChill controller, DF11 is the combined defrost start setpoint used when Pb4 (condenser probe 4) is configured as CF07 = 5. The controller monitors Pb3 falling below DF03 to start the DF10 interval countdown. When DF10 expires, the system checks Pb4 against DF11 — if Pb4 is below DF11, defrost starts; if not, the unit stays in heat pump mode until Pb4 drops below DF11.
Symptoms
- Defrost does not start despite DF10 expiring (Pb4 has not yet fallen below DF11 setpoint).
- Defrost triggers only after combined conditions of DF10 elapsed and Pb4 below DF11 are both met.
- DF11 functionality only active when CF07 = 5 and CF06 = 1 or 2.
Common causes
- DF11 set too low — system requires Pb4 to drop to very cold temperatures before combined defrost triggers.
- CF07 not set to 5, so the combined defrost logic and DF11 are not active.
- Pb4 probe fault causing incorrect reading that prevents the DF11 condition from being met.
- Actual outdoor conditions not cold enough to satisfy both DF10 and DF11 simultaneously.
Diagnostic steps
- 01
Verify CF07 = 5 configuration
Access the CF sub-menu on the IC100CX. Confirm CF07 = 5 to enable combined defrost mode using Pb4. If CF07 is set differently, DF11 is not used.
- 02
Verify CF06 setting
DF11 combined logic also requires CF06 = 1 or 2 (Pb3 configured appropriately). Confirm the probe assignment is correct for the system wiring.
- 03
Check DF11 setpoint value
Access the DF sub-menu and confirm DF11 is set to a temperature or pressure that represents a genuine icing condition on the Pb4 probe. Adjust to match system field conditions.
- 04
Verify Pb4 probe reading
View the Pb4 reading on the IC100CX display. Compare to an independent measurement at the Pb4 sensor location. A faulty probe causes the combined defrost condition to never be satisfied.
- 05
Review DF12 (combined defrost end setpoint)
DF12 sets the Pb4 temperature above which the combined defrost cycle stops. Confirm DF12 is set correctly to terminate the defrost once the coil is sufficiently clear of ice.
Keep this fix — get it by email with every Dixell/Copeland error code
A clean printable version of this Dixell/Copeland F11 guide + the full Dixell/Copeland code pack (59 codes), straight to your inbox. Free.
When to call a professional
Combined defrost configuration using Pb3 and Pb4 requires careful commissioning to match the heat pump system design and outdoor coil thermal characteristics. A licensed HVAC/R technician familiar with the Dixell IC100CX combined defrost feature should configure DF11 and DF12 during initial system setup and seasonal calibration.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Dixell/Copeland error codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
F7(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
F8(AF15) time When theinput is disable: according to the working algorithm. turn o
F1(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
F2AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
F12) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
E2Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
AL11temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
AL10events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc