Dixell/Copeland F3 Error Code
If Ar31=2 or3 and CF07=3 If CF01=3 and CF07≠6 Configuration Two digital inputs h
Source: IC100CX_QRG_GB.pdf
What does Dixell/Copeland F3 mean?
The F3 alarm on the Dixell IC100CX iChill controller is a configuration alarm triggered when two digital inputs are activated simultaneously in a configuration where CF01=3 and CF07 is not equal to 6 (or Ar31=2/3 with CF07=3). This indicates a hardware or wiring conflict between digital input assignments that prevents normal operation of the associated circuit.
Symptoms
- F3 displayed on the IC100CX screen.
- Alarm icon illuminated on the display.
- Affected digital input-controlled outputs may not function correctly.
- System may restrict operation on the affected circuit.
Common causes
- Two digital inputs both active simultaneously in a configuration that expects exclusive activation.
- Wiring error causing both digital inputs to read active at the same time.
- Configuration parameter mismatch — CF01 and CF07 set inconsistently for the installation.
- Failed digital input relay or field device holding both inputs in the active state.
Ask the AskWhiz AI about Dixell/Copeland F3
AskWhiz
online
Diagnostic steps
Identify conflicting digital inputs
Access the IC100CX digital input status screen and identify which two inputs are simultaneously active. Note their terminal numbers and cross-reference with the site wiring diagram.
Check field wiring for shorts or miswiring
Inspect wiring at both digital input terminals for accidental shorts between the two input circuits. Check for crossed wires or shared common connections causing simultaneous activation.
Inspect the connected field devices
Test each external device (relay, switch, or contactor) wired to the conflicting inputs. Verify contacts open and close correctly and do not both close at the same time during normal operation.
Review CF01 and CF07 configuration parameters
Access the configuration parameters and confirm CF01 (circuit 1 configuration) and CF07 settings match the actual hardware wiring and the commissioning documentation for the installation.
Correct the configuration or wiring
Either correct the field wiring to eliminate the simultaneous activation condition or adjust the CF parameters to match the actual wiring scheme. Power cycle the controller after changes.
When to call a professional
Engage the original commissioning technician or a Dixell-authorized service engineer if the CF01 and CF07 configuration parameters need to be changed, as incorrect configuration can alter fundamental circuit behavior. Parameter changes on iChill controllers should be documented and validated against the original system design.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com