Dixell/Copeland F4
Configuration alarmicon lighted Alarm code on display CF28= 1 & digital input no
Source: IC100CX_QRG_GB.pdf
What does Dixell/Copeland F4 mean?
The F4 alarm on the Dixell IC100CX iChill controller is a configuration alarm that activates when CF28 is set to 1 but the corresponding digital input is not active. The controller lights the alarm icon and displays the alarm code on screen. This indicates a mismatch between what the controller configuration expects from a digital input and what is actually present at that input terminal.
Symptoms
- F4 displayed on the IC100CX controller screen.
- Alarm icon illuminated on the display.
- Digital input expected by CF28 configuration reads inactive.
- Affected function or circuit controlled by this input does not operate as configured.
Common causes
- CF28 set to 1 but the corresponding field device or external contact is not wired or not closing.
- Field device wired to the digital input has failed open.
- Wiring break or loose connection on the digital input terminal.
- CF28 accidentally enabled during commissioning or parameter change without corresponding field wiring.
Diagnostic steps
- 01
Identify the CF28-assigned digital input
Access the IC100CX configuration parameters and note which digital input terminal is assigned by CF28. Navigate to the digital input status screen and confirm that input is reading inactive.
- 02
Inspect the wiring at the digital input terminal
Check wiring at the IC100CX digital input terminal for the CF28-assigned input. Look for loose terminal screws, broken wire ends, or missing jumpers if a hardwired input is expected.
- 03
Test the field device
Locate and test the external device wired to the CF28 digital input with a multimeter. Confirm it closes its contact under the expected operating condition.
- 04
Verify CF28 configuration intent
Confirm with the commissioning documentation whether CF28=1 is intentional for this installation. If the feature it enables is not used, setting CF28=0 eliminates the alarm without field wiring changes.
- 05
Correct wiring or parameter setting
Either install the correct field wiring to satisfy the CF28 digital input requirement, or set CF28=0 if the feature is not needed. Power cycle the controller and verify the F4 alarm clears.
Keep this fix — get it by email with every Dixell/Copeland error code
A clean printable version of this Dixell/Copeland F4 guide + the full Dixell/Copeland code pack (59 codes), straight to your inbox. Free.
When to call a professional
Call a Dixell-authorized commissioning technician if the purpose of the CF28 parameter is unclear from available documentation, or if the installation requires reconfiguration that affects multiple interrelated configuration parameters beyond CF28 alone.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Dixell/Copeland error codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
F7(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
F8(AF15) time When theinput is disable: according to the working algorithm. turn o
F1(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
F2AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
F12) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
E2Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
AL11temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
AL10events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
AL06; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
AL07. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
AL24. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com