Manitowoc Ice E07
Starving TXV or low on charge — evaporator inlet/outlet (T3/T4) spread over 12°F, 10 consecutive checks
Source: Manitowoc Ice/i0500a__man-indigo-r290-sth038-th.pdf
What does Manitowoc Ice E07 mean?
Code E07 is the starving-TXV / low-on-charge fault. The board compared the average evaporator inlet (T3) and outlet (T4) temperatures and saw a spread greater than 12°F on ten consecutive checks — the signature of an evaporator being fed too little refrigerant, either because the TXV is underfeeding or the system is short on charge.
Symptoms
- E07 logged, often with thin or incomplete ice at the evaporator outlet
- Long freeze cycles and falling production
- Frost pattern uneven along the evaporator
Common causes
- Low refrigerant charge (leak)
- TXV underfeeding or partially restricted
- Restricted filter-drier starving the evaporator
Diagnostic steps
- 01
Confirm the symptom
Check the ice-fill pattern and freeze times; thin-at-outlet ice with long freezes matches a starving evaporator.
- 02
Rule out the easy causes
Confirm the condenser is clean and the machine isn't in an extreme ambient; heat problems can masquerade as charge problems.
- 03
Leak-check before topping up
This machine is critically charged — a low charge means refrigerant left the system; find and fix the leak, then weigh in the nameplate charge exactly.
- 04
Evaluate TXV/drier
If charge is verified correct, evaluate the TXV and filter-drier for underfeed/restriction per the refrigeration diagnostics section.
Keep this fix — get it by email with every Manitowoc Ice error code
A clean printable version of this Manitowoc Ice E07 guide + the full Manitowoc Ice code pack (44 codes), straight to your inbox. Free.
When to call a professional
Refrigeration-circuit work on this machine (gauges, refrigerant recovery, TXV or compressor replacement) requires an EPA-certified refrigeration technician, and Indigo units built on R290 propane additionally require flammable-refrigerant service procedures. If the fault returns after the basic checks here, book a qualified ice-machine technician rather than continuing to reset the unit.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Manitowoc Ice error codes
Safety Limit 1 - freeze cycle ran too long (long freeze)
SL#2Safety Limit 2 - harvest cycle ran too long (long harvest)
SL#3Safety Limit 3 - no water sensed during the freeze cycle
E01Long freeze cycle — freeze ran to the 60-minute limit; 6 consecutive trigger the SL#1 shutdown
E02Long harvest cycle — harvest hit the 3.5-minute limit; repeated events log SL#2
E03Input power loss recorded in the event log on power-up (event-log entry only, no alarm)
E04High condenser temperature — liquid line too hot (air- or water-cooled condenser fault)
E05High-pressure control opened — the HPCO safety switch tripped on excess discharge pressure
E08TXV fault (dual-circuit/single-evaporator models) — evaporator underfeed signature
E09Evaporator flooding, circuit 1 — early-freeze discharge temperature below the 6-cycle average
E10Evaporator flooding, circuit 2 (dual-TXV) — early-freeze discharge temperature below the 6-cycle average
E11Refrigeration fault — refrigeration-side abnormality; run full system diagnostics