Carel AL001 Error Code
Error in the number of retain memory writings Man Imm. AL002 AL003 AL004 Error i
Source: 0300081EN.pdf
What does Carel AL001 mean?
AL001 on the Carel Heos system chiller controller (0300081EN) indicates an error in the number of retain memory writings. The controller has exceeded the allowed frequency of writes to its retain (non-volatile) memory storage area, which triggers this alarm to protect memory longevity. Manual reset is required and the alarm does not cause any system shutdown on its own.
Symptoms
- AL001 displayed on the Heos system controller.
- No direct impact on chiller or pump operation at the AL001 level alone.
- Manual reset is required to clear the alarm.
- Repeated AL001 events indicate accelerating memory write frequency.
Common causes
- Application variables that are written to retain memory are changing at an excessively high rate.
- Controller firmware fault causing abnormal retain memory write frequency.
- Unstable input signals (e.g., fluctuating analog sensor) triggering repeated parameter saves.
- External supervisory system sending excessive write commands to retain variables.
- Hardware deterioration of the retain memory chip nearing end of write cycle life.
Ask the AskWhiz AI about Carel AL001
AskWhiz
online
Diagnostic steps
Record and manually reset AL001
Note the date and time of AL001 in the service log. Manually reset the alarm from the Heos system controller alarm menu.
Check for accompanying alarms that may indicate root cause
Review the full alarm log. If AL001 appears alongside frequent sensor alarms or communication errors, unstable inputs may be driving excessive memory writes.
Inspect sensor inputs for unstable or noisy signals
Check all analog sensor inputs connected to the pCO controller for noise or oscillation. Shield sensor cables separately from power wiring.
Review supervisory system write commands
If a BMS or supervisory system is connected, verify it is not issuing excessive setpoint writes to the controller at a rate that stresses retain memory.
Monitor recurrence frequency
If AL001 recurs frequently (more than a few times per day), escalate to a Carel-authorized technician for deeper diagnostics of the retain memory health.
When to call a professional
If AL001 recurs frequently or is accompanied by AL002 (retain memory write error), the controller's non-volatile memory may be approaching failure. Controller board replacement requires a Carel-certified technician who can restore system configuration and re-commission the chiller.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com