Carel AL005 Error Code
LT Pump alarm Auto Imm. AL006 Chillbooster alarm Auto Imm. Chillbooster OFF AL00
Source: 0300081EN.pdf
What does Carel AL005 mean?
AL005 on the Carel Heos system controller indicates an LT (low-temperature) pump alarm. The controller has received a fault signal from the LT pump circuit — either from a flow switch, thermal overload, or the pump's alarm contact. The controller responds with an automatic reset and cuts off the LT pump immediately upon alarm activation.
Symptoms
- AL005 displayed on the Heos system controller.
- LT pump shuts off immediately upon alarm.
- LT Chiller loses its water circuit — LT cooling load is interrupted.
- Automatic reset is attempted; pump may restart if the fault clears.
Common causes
- LT pump thermal overload protector has tripped due to overcurrent.
- LT pump motor has failed — winding fault or bearing seizure.
- LT pump flow switch has opened, indicating no flow in the water circuit.
- Air lock or blockage in the LT pump suction line preventing flow.
- Low water level in the LT circuit expansion vessel causing pump cavitation.
Ask the AskWhiz AI about Carel AL005
AskWhiz
online
Diagnostic steps
Check the LT pump for operation
Verify the LT pump is running — listen for motor noise and feel for vibration. A pump that is energized but not running indicates a seized motor or blocked impeller.
Inspect the LT pump thermal overload
Check the thermal overload relay on the LT pump motor starter. If tripped, reset it and measure motor current on all three phases to confirm it is within nameplate ratings.
Check LT circuit water pressure and flow
Verify water pressure in the LT circuit and confirm flow switch operation. A closed flow switch with no flow indicates air lock, blockage, or pump failure.
Bleed air from the LT circuit
Open air vent valves on the LT circuit high points to remove any trapped air that could cause pump cavitation and flow loss.
Inspect LT pump strainer
Check the suction strainer on the LT pump for debris blockage. Clean the strainer basket if restricted.
When to call a professional
If the LT pump motor has failed, shows winding faults, or the pump assembly requires replacement, contact a qualified mechanical technician. Pump replacement on a pressurized hydronic circuit requires proper system isolation, de-pressurization, and recommissioning. Continued operation of the LT circuit without a functioning pump will damage the LT chiller.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com