Carel AL007
Clock card broken A None No AL008 Memory expansion damaged AM None No AL009 Remo
Source: 030221536.pdf
What does Carel AL007 mean?
AL007 on the Carel FLSTDmSCHE screw chiller controller indicates the real-time clock card is broken or not communicating with the pCO5 main board. The clock card is required for alarm logging with timestamps, time-band scheduling, and timed rotation of compressors and pumps. AL007 is a signal-only alarm with automatic reset — the chiller continues cooling, but time-dependent functions are unavailable.
Symptoms
- AL007 displayed on the pCO5 terminal; chiller continues running
- Alarm log timestamps absent or showing incorrect dates/times
- Time-band setpoint schedules and timed maintenance intervals not executing
Common causes
- Real-time clock battery depleted — the lithium battery backing the clock card has failed
- Clock card not seated correctly on the pCO5 or pCO3 board
- Clock card hardware failure — the module itself has failed
- Firmware update or parameter reset that disabled the clock card interface
Diagnostic steps
- 01
Check clock card seating
Power down the chiller controller and inspect the optional clock board connector on the pCO5 main board. The clock card should be firmly seated with no bent pins. Re-seat it if loose.
- 02
Replace the clock battery
The pCO5 clock card uses a replaceable lithium coin cell (typically CR2032). If the battery voltage is low or zero, replace it. The battery can be replaced with the controller powered on to preserve clock settings.
- 03
Set the correct date and time
After battery replacement, navigate to the clock parameter screens on the pCO5 terminal and set the correct date and time. Reset all time-band programming that may have been lost.
- 04
Check for clock card module failure
If the alarm persists after battery replacement and re-seating, the clock module itself may have failed. Test by replacing the clock card with a known-good unit.
- 05
Verify automatic reset
AL007 resets automatically once the clock card communicates successfully. Confirm the alarm clears, the correct time is displayed, and alarm log entries now include timestamps.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL007 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
Battery replacement and clock card re-seating are straightforward tasks for a qualified controls technician. If the alarm persists after both steps, a Carel-authorized service technician should diagnose the pCO5 board interface. Continued operation without a working clock card means alarm timestamps and timed maintenance schedules are unreliable.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.it