Carel AL008 Error Code
AL009 AL010 MT Pump 1 Overload alarm AC System alarm MT Pump 2 Overload alarm Au
Source: 0300081EN.pdf
What does Carel AL008 mean?
AL008 on the Carel Heos system controller indicates an AC (air conditioning) system alarm. The controller has received a fault signal from the connected AC system — typically a chiller or DX unit connected to the Heos MT or LT water circuit — and shuts off the AC system output command. The alarm resets automatically and activates immediately upon detection.
Symptoms
- AL008 displayed on the Heos system controller.
- AC system output command is de-energized.
- The connected air conditioning system stops operating.
- Automatic reset is attempted by the controller.
Common causes
- The connected AC unit's own internal alarm contact has opened (e.g., DX unit high pressure, low pressure, or inverter fault).
- Wiring fault on the digital input carrying the AC system alarm signal to the pCO.
- Power supply interruption to the AC system.
- AC system commissioning incomplete — alarm input not correctly configured in the pCO.
Ask the AskWhiz AI about Carel AL008
AskWhiz
online
Diagnostic steps
Check the connected AC system for local alarms
Access the AC system's own controller or display and identify any active alarms. The AC unit's internal fault is the most common cause of AL008 on the Heos system.
Inspect the AC system alarm digital input wiring
Trace the wiring from the AC system alarm contact to the Heos pCO digital input. Verify the wiring is intact and the contact state matches what the pCO configuration expects.
Verify AC system power supply
Confirm the AC unit has power and all local circuit breakers are closed. A power interruption to the AC system will open its alarm contact and trigger AL008.
Clear the AC unit alarm
Resolve the AC system's internal alarm condition per the AC manufacturer's procedures. Once the AC unit alarm is cleared, the contact should close and AL008 should auto-reset.
Confirm AL008 clears
Verify AL008 clears automatically after the AC system fault is resolved and the alarm contact returns to the normal (closed) position.
When to call a professional
Diagnosing the AC unit's internal fault (e.g., refrigerant circuit pressure fault, inverter fault) requires the manufacturer's service documentation for that specific AC unit and may require a refrigeration technician. If the Heos pCO digital input wiring or configuration is the issue, a Carel-authorized technician should be contacted.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com