Carel AL011 Error Code
Compensation probe broken or disconnected A None 10s AL012 Suction press.circ.1
Source: 030221536.pdf
What does Carel AL011 mean?
AL011 on the Carel FLSTDmSCHE screw chiller is the first custom general alarm — a user-defined input that signals a site-specific condition monitored by the pCO5 controller. The alarm text and trigger source are configured by the commissioning technician. When AL011 fires, the controller shuts down the unit and all compressors in a controlled sequence. This is a manual-reset alarm.
Symptoms
- AL011 displayed on pCO5 terminal with full unit controlled shutdown
- The display description may show a custom text label set during commissioning
- All compressors stopped; cooling output lost
Common causes
- The digital input or network variable configured as AL011's trigger has opened or signaled an alarm state
- External safety device connected to the AL011 input has operated — e.g., smoke detector, flood sensor, or remote interlock
- Wiring fault on the AL011 digital input causing a false open-circuit trigger
- Commissioning error — wrong input or inverted polarity assigned to AL011
Ask the AskWhiz AI about Carel AL011
AskWhiz
online
Diagnostic steps
Identify the AL011 trigger source
Check the chiller commissioning records or the pCO5 configuration to identify which digital input or network variable is assigned to AL011 and what external device it monitors.
Inspect the triggering device
Go to the physical location of the device connected to the AL011 input. Check whether the device has actually operated (e.g., a water detector sensing moisture, an interlock contact open) or if the wiring has failed.
Check wiring continuity on the AL011 input
With the controller powered down, measure continuity on the AL011 digital input cable. An open circuit where a closed contact is expected confirms a wiring break rather than a genuine safety event.
Resolve the triggering condition
If a genuine safety event occurred (e.g., flooding, fire), resolve the hazard before resetting the alarm. If the trigger was a wiring fault, repair the cable and re-terminate the input.
Manually reset AL011
Press the ALARM button on the pCO5 terminal to reset AL011 after the cause is resolved. The unit will restart and begin loading compressors according to the normal control sequence.
When to call a professional
If AL011 is connected to a safety device (fire, gas, or flood detection system), do not reset the alarm until the safety hazard is evaluated and cleared by the appropriate professional. For wiring faults that are difficult to trace in multi-conductor control cables, a licensed electrician or controls technician should perform the diagnosis.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.it