Carel AL013 Error Code
Device offline alarm Auto Imm. AL014 Wrong configuration on device Auto Imm. AL0
Source: 0300081EN.pdf
What does Carel AL013 mean?
AL013 signals that a device on the µChiller pLAN network has gone offline. The controller detected a loss of communication with a connected module or expansion card during normal operation. This is a serious alarm that triggers an immediate automatic reset and halts the affected circuit until the network link is restored.
Symptoms
- Controller display flashes AL013 with an immediate alarm notification.
- Affected refrigerant circuit shuts down automatically.
- Buzzer activates and the Alarm button lights up on the user terminal.
- pLAN network communication indicator shows a fault condition.
Common causes
- Loose or damaged pLAN network cable between the main controller and expansion module.
- Faulty or powered-off expansion card or peripheral device.
- Incorrect network address configuration on the connected device.
- Power interruption to a remote module on the pLAN bus.
Ask the AskWhiz AI about Carel AL013
AskWhiz
online
Diagnostic steps
Inspect pLAN wiring connections
Check all network cables connecting the main µChiller controller to expansion modules. Reseat any loose connectors and inspect for damaged insulation or broken conductors.
Verify device power supply
Confirm that the offline device has power by checking its indicator LEDs. Measure supply voltage at the device terminals and compare to the rated specification.
Check pLAN network addresses
Enter the manufacturer programming level and verify that each connected device has a unique, correctly assigned network address. Duplicate addresses cause communication failures.
Restart the controller and monitor alarms
Power cycle the µChiller controller after correcting any wiring or configuration issues. Monitor the alarm log to confirm AL013 clears and does not recur.
When to call a professional
Call a licensed refrigeration technician if AL013 persists after verifying all pLAN wiring and address settings. Diagnosing faulty expansion boards, replacing network communication modules, or re-flashing firmware requires specialized Carel tools and authorization. Repeated offline alarms may indicate deeper electronic failure that can damage compressor circuits if left unresolved.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, docs.quecalor.com