Carel AL016 Error Code
AL017 LT Pump 1 Overload alarm Source pump LT group alam T Pump 2 Overload alarm
Source: 0300081EN.pdf
What does Carel AL016 mean?
AL016 indicates a thermal overload alarm on LT (Low Temperature) pump 1 in the µChiller system. The pump motor protection relay has tripped, signaling that the pump drew excessive current for long enough to activate its thermal protector. The unit shuts down to prevent motor damage.
Symptoms
- LT pump 1 stops running immediately on alarm activation.
- Unit or circuit shuts down depending on pump role in the system.
- AL016 flashes on the controller display alongside the buzzer alarm.
- Thermal overload relay on the pump motor panel is tripped.
Common causes
- Pump motor thermal overload relay has tripped due to sustained overcurrent.
- Blocked or partially closed isolation valve restricting pump flow.
- Worn pump bearings causing increased mechanical resistance and motor load.
- Incorrect overload relay setting too low for the installed pump.
- Phase imbalance or single-phasing on the pump motor power supply.
Ask the AskWhiz AI about Carel AL016
AskWhiz
online
Diagnostic steps
Locate and reset the thermal overload relay
Find the motor protection relay in the electrical panel. Allow the motor to cool for at least 15 minutes, then press the manual reset button on the overload relay.
Check pump isolation valves
Verify all isolation valves in the LT pump circuit are fully open. A partially closed valve increases head pressure, overloads the motor, and trips the overload.
Measure motor current on all phases
Use a clamp meter to measure running current on each phase while the pump operates. Compare against the motor nameplate FLA rating. Investigate any phase imbalance exceeding 5%.
Inspect pump mechanically
Check for seized bearings or impeller obstructions by attempting to rotate the shaft by hand with power off. Replace bearings or clear impeller blockage as needed.
Verify overload relay settings
Confirm the overload relay trip current is set to match the motor nameplate FLA. Adjust within the allowable range if found incorrectly configured.
When to call a professional
Engage a licensed technician if the thermal overload trips repeatedly after reset, if you measure phase imbalance or low voltage at the motor terminals, or if the pump shaft is seized. Motor replacement, electrical supply repairs, and pump assembly work require professional tools and refrigerant system expertise to avoid water-side damage to the chiller.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, docs.quecalor.com