Carel AL02 Error Code
Compressor 2 general alarm (High pressure -Compressor circuit breaker - Condense
Source: 030221471.pdf
What does Carel AL02 mean?
AL02 is the general compressor alarm for Compressor 2 in the Carel Standard Air-Conditioners program. It activates when the digital input assigned to Compressor 2's thermal overload, high-pressure cutout, or circuit breaker opens. The controller immediately stops Compressor 2 to protect it from damage. Reset requires manual intervention at the controller after the protection device has been reset.
Symptoms
- AL02 displayed on pCO terminal with Compressor 2 stopped immediately
- Compressor 2 contactor de-energized; Circuit 2 cooling capacity lost
- Alarm relay activates; buzzer sounds on external terminal
Common causes
- High discharge pressure tripped the high-pressure cutout on Compressor Circuit 2
- Compressor 2 thermal overload operated due to overcurrent or motor winding temperature
- Compressor 2 circuit breaker tripped on electrical fault or sustained overload
- Loose or open wiring on the alarm digital input for Compressor 2
Ask the AskWhiz AI about Carel AL02
AskWhiz
online
Diagnostic steps
Identify the protection device that operated
Locate the compressor protection panel for Circuit 2. Check whether the high-pressure cutout, thermal overload relay, or circuit breaker has tripped. The protection device will be in a visible tripped or open state.
Investigate and resolve the root cause
For high pressure: inspect condenser airflow, fan operation, and refrigerant charge. For thermal overload: check supply voltage, current draw, and motor winding resistance. For circuit breaker: verify no electrical fault before resetting.
Reset the protection device
After resolving the root cause, manually reset the high-pressure cutout, thermal overload, or circuit breaker per its manufacturer instructions. Do not bypass or jumper protection devices.
Check and re-seat digital input wiring
With power off, inspect the alarm digital input wire on the pCO board for Circuit 2. A loose wire at the screw terminal will cause a false AL02 that clears with no apparent cause.
Reset the controller alarm and verify restart
Press the ALARM button on the pCO terminal to reset AL02. The safety timer must expire before Compressor 2 restarts. Monitor system pressures and current draw on the first restart cycle.
When to call a professional
If Compressor 2 trips repeatedly on AL02 within hours of each reset, a licensed HVAC/R technician must diagnose the root cause. Recurring high-pressure trips require refrigerant circuit analysis. Repeated thermal overloads may indicate a failing compressor motor. Any situation where the protection device cannot be identified or safely reset must be handled by a qualified technician with proper recovery equipment.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com