Carel AL020 Error Code
External humidity probe alarm Auto Fb03 AL021 AL022 Drycooler inlet water temper
Source: 0300081EN.pdf
What does Carel AL020 mean?
AL020 is an external humidity probe alarm on the µChiller system. The controller has detected that the analog signal from the external ambient humidity probe is out of its configured valid range — either a disconnected probe wire, a short circuit, or a failed sensor element. Control logic that depends on humidity input is degraded until the probe is restored.
Symptoms
- AL020 flashes on the controller display with buzzer activation.
- External humidity reading shows an invalid or frozen value.
- Functions using the humidity input (e.g., drycooler control, free cooling compensation) may default to fallback settings.
- Alarm relay activates depending on controller configuration.
Common causes
- Humidity probe cable disconnected or broken at the terminal block.
- Short circuit in the probe wiring to the controller analog input.
- Probe sensor element failed due to age, moisture ingress, or damage.
- Incorrect probe type configured in parameters not matching installed hardware.
- Probe supply voltage absent or outside tolerance.
Ask the AskWhiz AI about Carel AL020
AskWhiz
online
Diagnostic steps
Inspect probe wiring at the terminal block
Power down and check the signal and supply wires at the controller input terminal. Tighten any loose connections and look for chafed or broken conductors.
Measure probe supply voltage
With power on, measure the 24 V supply to the probe. No voltage indicates a blown fuse or wiring fault upstream of the probe.
Check probe output signal
Measure the analog output of the probe (typically 4–20 mA or 0–10 V). A reading of 0 mA or 0 V when supply is present usually indicates a failed sensor or open circuit.
Verify probe configuration parameters
In the service programming level, confirm the probe type and input range match the physical sensor installed. A mismatch causes the controller to reject in-range signals.
Replace the probe if defective
If wiring and configuration are correct but the signal is still invalid, replace the humidity probe with a Carel-approved equivalent and recalibrate if required.
When to call a professional
Engage a qualified technician if replacing the probe does not resolve the alarm, or if the analog input card itself is suspected. Input module replacement and system reconfiguration require Carel parameter-level access and calibration tools to restore correct dew-point compensation and free-cooling control.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, docs.quecalor.com