Carel AL021 Error Code
High condensing temp. alarm circuit 1 Compressor1 OFF in contrlled shutdown Para
Source: 030221536.pdf
What does Carel AL021 mean?
AL021 activates on the Carel FLSTDmSCHE screw chiller when the condensing temperature on Circuit 1 exceeds the configured alarm threshold. Elevated condensing temperature indicates the condenser cannot reject sufficient heat, which raises discharge pressure and risks damage to the compressor. The controller shuts down Compressor 1 in a controlled sequence. This alarm has automatic reset after the condensing temperature drops below the threshold.
Symptoms
- AL021 displayed on pCO5 terminal with Compressor 1 in controlled shutdown
- Condensing temperature probe reading above the alarm setpoint on the controller display
- Condenser fans running at maximum speed attempting to reduce head pressure
Common causes
- Condenser coil fouled with dirt, debris, or biological growth reducing airflow and heat transfer
- Condenser fan failure reducing airflow across the coil on Circuit 1
- Ambient temperature exceeding the chiller's rated design conditions
- Refrigerant overcharge causing excessively high condensing pressure and temperature
- Condenser airflow short-cycling — hot discharge air recirculating back into condenser intake
Ask the AskWhiz AI about Carel AL021
AskWhiz
online
Diagnostic steps
Check condenser fan operation on Circuit 1
Confirm all fans assigned to Circuit 1's condenser are running at full speed. A failed fan motor or seized bearing drastically reduces condenser capacity.
Inspect and clean the condenser coil
With fans off, inspect the condenser fins for dirt, lint, or debris. Clean with low-pressure water spray from inside out, or use an approved coil cleaner. Even 10–15% fin blockage raises condensing temperature significantly.
Check for airflow short-cycling
Verify the condenser discharge air has a clear path away from the unit and is not recirculating back into the condenser intake. Remove any obstructions around the unit within the recommended clearances.
Verify refrigerant charge
With the chiller running and all compressors loaded, compare suction and discharge pressures against the refrigerant pressure-temperature chart. Overcharge produces abnormally high discharge temperature with normal suction superheat.
Allow auto-reset and monitor
AL021 resets automatically once condensing temperature drops below the alarm threshold. After the root cause is resolved, monitor condensing temperature on the next operating cycle to confirm it stays within the setpoint.
When to call a professional
Refrigerant charge adjustment requires EPA 608 certification. If condenser cleaning and fan verification do not resolve AL021, a licensed HVAC/R technician with manifold gauges should perform a full system diagnostic. Repeated high condensing temperature alarms that correlate with ambient conditions may require engineering review of the installed condenser capacity relative to site-specific thermal loads.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.it