What does Carel AL022 mean?
AL022 on the Carel FLSTDmSCHE screw chiller indicates a battery alarm for Circuit 1's EVD electronic expansion valve driver. The EVD evolution driver uses a backup battery or capacitor module (EVBAT) to close the expansion valve on power failure. AL022 signals that this backup power source has discharged, is absent, or has detected an abnormality. The controller logs the alarm but takes no shutdown action — it is a signal-only event with automatic reset.
Symptoms
- AL022 displayed on pCO5 terminal; unit continues operating normally
- EVD Driver 1 battery/backup module status indicator may show discharged or fault state
- Risk of incomplete valve closing on next power failure
Common causes
- EVBAT capacitor or battery module has depleted and needs recharging time after recent power restoration
- EVBAT backup module not installed on EVD Driver 1
- EVBAT module internal fault — capacitors have degraded beyond service life
- Intermittent power supply issue causing the EVBAT module to not charge fully
Ask the AskWhiz AI about Carel AL022
AskWhiz
online
Diagnostic steps
Verify EVBAT module presence
Inspect EVD Driver 1 for the EVBAT00400 or EVBAT00500 backup power module. It mounts on the DIN rail adjacent to the driver. If not installed, the system is not protected against valve-open power failures.
Allow module to fully charge
After a power restoration event, the EVBAT module requires 4–5 minutes to fully charge (or longer for some valve types). AL022 should clear automatically once the module reaches full charge.
Inspect EVBAT module condition
Check the EVBAT module for physical damage, swollen capacitors, or discolored components. Modules have a finite service life and should be replaced per Carel's recommended maintenance interval.
Test backup close function
With the system running and the EVBAT charged, perform a controlled power interruption to EVD Driver 1 and verify the expansion valve closes fully. Incomplete closing indicates a depleted or failed module.
Replace EVBAT module if defective
Replace a failed or life-expired EVBAT module with a new Carel unit. Confirm AL022 clears after the replacement module has had time to charge.
When to call a professional
EVBAT module replacement is a straightforward task for a qualified controls technician. If the alarm persists after module replacement and charging, the EVD Driver 1 internal battery monitoring circuit may be faulty, requiring Carel-authorized board service.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.it