Carel AL027 Error Code
LT inlet pressure probe alarm Auto Imm. AL028 LToutlet pressure probe alarm Auto
Source: 0300081EN.pdf
What does Carel AL027 mean?
AL027 indicates a fault on the LT circuit inlet pressure probe (refrigerant side). The pressure transducer at the LT circuit evaporator inlet has produced a signal outside the valid range, which disables the circuit immediately. Without reliable pressure data, the controller cannot safely operate the LT refrigerant circuit.
Symptoms
- LT circuit 1 shuts down immediately and logs AL027.
- LT inlet pressure reading is invalid or stuck at a limit value on the display.
- Controller alarm relay activates based on configured alarm relay setting.
- Buzzer sounds and Alarm LED flashes on the user terminal.
Common causes
- Pressure transducer signal wiring loose or disconnected at the controller.
- Transducer failed due to overpressure event or manufacturing defect.
- Incorrect probe type or range configured in service parameters.
- Short circuit in the signal cable causing a 0 mA or 0 V reading.
- Actual refrigerant pressure at the probe location outside the transducer measurement range.
Ask the AskWhiz AI about Carel AL027
AskWhiz
online
Diagnostic steps
Check probe connections at both ends
Verify the connector at the transducer body and the terminal at the controller are tight and undamaged. Loose signal wires at either end create intermittent false alarms.
Measure transducer output signal
With the system at known static pressure, measure the transducer analog output. On a 4–20 mA sensor, zero or non-proportional output at a known pressure confirms sensor failure.
Confirm configured pressure range
In service programming, check that the probe range parameter matches the installed transducer. Installing a 0–10 bar transducer with a 0–30 bar range configured creates out-of-range alarms.
Replace the transducer if failed
Recover refrigerant per applicable regulations before replacing the transducer. Install the correct pressure range replacement, leak-check the port, recharge, and restart.
When to call a professional
Refrigerant recovery and handling during transducer swap requires EPA 608 or equivalent certification. If the alarm persists after replacement, a qualified technician must evaluate actual refrigerant pressure levels and check the LT circuit for abnormal operating conditions that may be driving pressure outside the probe range.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, docs.quecalor.com