Carel AL029
Low Temperature alarm 1 Auto Fb03 AL030 Low Temperature alarm 2 Auto Fb03 AL031
Source: 0300081EN.pdf
What does Carel AL029 mean?
AL029 is a Low Temperature alarm on the µChiller system, triggered when the monitored chilled water or refrigerant temperature falls below the configured low-temperature threshold for a sustained period. This alarm protects the evaporator from freeze-up and the refrigerant circuit from abnormally low suction conditions.
Symptoms
- AL029 displayed on the controller with buzzer active.
- Chilled water outlet temperature or evaporator temperature below alarm setpoint.
- Circuit may shut down or reduce compressor capacity depending on configuration.
- Frost or ice formation visible on evaporator surfaces in severe cases.
Common causes
- Chilled water flow rate too low, causing excessive temperature drop across the evaporator.
- Low temperature alarm threshold set too high relative to design operating conditions.
- Refrigerant overcharge causing unusually low evaporation temperatures.
- Expansion valve malfunction allowing excessive refrigerant flow.
- System operating below design ambient conditions in cold weather applications.
Diagnostic steps
- 01
Verify chilled water flow rate
Check that the pump is running at design speed and that all isolation valves are open. Low flow is the most common cause of evaporator freeze-up leading to a low temperature alarm.
- 02
Review alarm setpoint parameters
Access the service level and compare the low-temperature alarm threshold to design operating conditions. Adjust the threshold within the allowable range if it was set incorrectly.
- 03
Check evaporator for ice formation
Inspect the evaporator visually or via temperature probes. Ice on the water-side or refrigerant-side indicates insufficient flow or incorrect refrigerant charge.
- 04
Inspect the expansion valve operation
Monitor superheat via the EVD driver display. Abnormally low or negative superheat confirms excessive refrigerant flow from a stuck-open or oversized valve.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL029 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
Contact a licensed refrigeration technician if the low temperature alarm persists after restoring adequate water flow, or if evaporator icing is confirmed. Refrigerant charge adjustment, expansion valve replacement, and evaporator defrost procedures require system recovery equipment and EPA 608 or equivalent certification.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, docs.quecalor.com