Carel AL03 Error Code
switch) Circuit 1 off Manual No Compressor 2 HP (pressure AL04 AL05 switch) Anti
Source: 030221501.pdf
What does Carel AL03 mean?
AL03 on Carel µChiller and pCO-based chiller controllers indicates that the high-pressure (HP) safety switch on compressor 2's refrigerant circuit has tripped. When refrigerant discharge pressure exceeds the switch's cutout setting, the contact opens and the controller shuts down compressor 2 circuit 1 with a manual-reset alarm. This is a critical safety protection to prevent compressor damage from over-pressure.
Symptoms
- AL03 displayed on the Carel controller.
- Compressor 2 is shut down; circuit 1 is off.
- High discharge pressure present or recently present on circuit 1.
- Manual reset required at the controller after the fault is resolved.
Common causes
- Condenser coils fouled or airflow blocked, preventing adequate heat rejection.
- Condenser fan motor failed, stopping airflow across the coil.
- Non-condensable gases (air) in the refrigerant circuit raising discharge pressure.
- Refrigerant overcharge causing elevated condensing pressure.
- High-pressure switch set point too low or device malfunctioning.
Ask the AskWhiz AI about Carel AL03
AskWhiz
online
Diagnostic steps
Identify the elevated pressure condition
Connect refrigerant gauges to compressor 2's high-side service port and record discharge pressure to confirm an actual over-pressure event.
Inspect the condenser section for compressor 2
Check condenser coils and fans serving circuit 1. Clean fouled coils and verify all condenser fans are rotating at correct speed.
Verify condenser airflow is unobstructed
Confirm the unit is not installed in an enclosure with recirculated discharge air. Ensure 1 m minimum clearance on all air intake and discharge sides.
Test the HP pressure switch
If discharge pressure is within normal range but AL03 tripped, the HP switch may be faulty. Test continuity across the switch contacts with pressure at a known normal value.
Reset the alarm at the controller
After correcting the root cause, reset AL03 manually at the controller and verify compressor 2 starts and runs without recurrence.
When to call a professional
Call a refrigeration engineer for all tasks involving refrigerant circuit pressure: attaching gauges, checking for non-condensables, or recovering and recharging refrigerant. HP switch replacement on a live system also requires lock-out/tag-out procedures that should only be performed by qualified personnel. Repeated HP trips without an obvious condenser fault suggest internal refrigerant system issues requiring thorough investigation.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com