Carel AL035 Error Code
AL036 AL258 AL259 Humidity probe inserial broken Ambient temperature probe alarm
Source: 0300081EN.pdf
What does Carel AL035 mean?
AL035 signals that a serial humidity probe on the µChiller network is offline or has broken communication. The controller expected data from a connected serial humidity sensor but did not receive a valid response within the timeout period. Humidity-dependent control functions such as free cooling enable/disable are suspended.
Symptoms
- AL035 displayed on controller with alarm notification.
- Serial humidity probe reading shows invalid or last-good frozen value.
- Humidity-dependent control modes revert to fallback or default behavior.
- Alarm relay activates per configured relay output assignment.
Common causes
- Serial bus cable disconnected or broken between the controller and humidity probe.
- Incorrect serial address configured on the probe or in controller parameters.
- Humidity probe powered off or failed internally.
- Serial communication interference from nearby electrical equipment.
- Probe firmware version incompatible with the controller.
Ask the AskWhiz AI about Carel AL035
AskWhiz
online
Diagnostic steps
Inspect serial bus wiring to the probe
Check the RS-485 or pLAN bus cable connecting the humidity probe. Verify polarity (A/B) is correct and that both ends are securely terminated at the controller and probe.
Verify probe serial address
Confirm the probe's configured serial address matches the address assigned to it in the controller's serial device table. Address conflicts with other devices cause communication failures.
Check probe power supply
Measure the supply voltage at the probe terminals. If absent, trace the supply circuit for a blown fuse or open wire.
Check for serial bus interference
Ensure the serial cable is routed away from power cables and inverter drives. Add termination resistors at cable ends if the bus run exceeds the recommended maximum length.
Replace the probe if diagnostics fail
If wiring, power, and addressing are all confirmed correct, replace the humidity probe. Use a Carel-compatible serial humidity sensor with matching protocol and firmware.
When to call a professional
Involve a qualified Carel technician if the serial bus configuration involves multiple networked devices that are difficult to diagnose in the field, or if the alarm occurs alongside other pLAN communication faults suggesting a bus-level issue. Reprogramming serial device tables at the manufacturer level requires Carel access credentials.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, docs.quecalor.com