Carel AL06
AL07 AL08 High ambient temperature Low ambient temperature Compressor 1 LP in co
Source: 030221501.pdf
What does Carel AL06 mean?
AL06 on Carel µChiller and pCO chiller controllers signals a high ambient temperature alarm. The controller monitors outdoor or machine-room air temperature and activates AL06 when it exceeds the configured upper ambient limit. High ambient temperature reduces refrigeration system efficiency and can push compressor discharge pressure and temperature beyond safe operating limits, potentially causing other protective alarms to cascade.
Symptoms
- AL06 displayed on the Carel controller.
- Outdoor or machine-room air temperature is above the maximum ambient design limit.
- System cooling capacity is reduced due to elevated condensing temperature.
- Compressor high-pressure protection alarms may also appear concurrently.
Common causes
- Ambient air temperature genuinely exceeds the chiller's rated maximum (often 45–50 °C).
- Condenser discharge air is recirculating back to the inlet in a confined installation.
- Insufficient clearance around the unit causing heat buildup in the machine room.
- Ambient temperature probe fault reporting false high readings.
Diagnostic steps
- 01
Verify ambient temperature with an independent thermometer
Measure air temperature at the unit's air intake using a calibrated thermometer to confirm whether the ambient is genuinely above the alarm setpoint.
- 02
Check for discharge air recirculation
Inspect the installation to ensure warm condenser exhaust air is not returning to the air intake. Add baffles or increase clearances if needed.
- 03
Improve machine room ventilation
If the unit is installed indoors, confirm ventilation is adequate. Machine rooms require sufficient fresh-air intake and exhaust airflow for rated ambient conditions.
- 04
Check the ambient temperature probe
Inspect the ambient probe wiring and placement. Verify the probe is positioned in free air away from heat sources, and test probe resistance to rule out a sensor fault.
- 05
Reduce load or schedule operation for cooler periods
If ambient conditions routinely exceed design limits, consult the chiller manufacturer about de-rating or operational scheduling.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL06 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
Consult a refrigeration engineer if AL06 occurs alongside HP alarms or if the chiller is being operated in an environment that regularly exceeds its ambient design rating. Persistent high-ambient operation damages compressor windings and oil. An engineer can advise on de-rating, additional ventilation, or the need for a high-ambient condenser upgrade.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com