Carel AL09 Error Code
(pressure switch) Compressor 2 LP in cooling (pressure switch) Comp. 2 OFF Manua
Source: 030221501.pdf
What does Carel AL09 mean?
AL09 on Carel µChiller and pCO chiller controllers indicates that the low-pressure (LP) safety switch on compressor 2's cooling circuit has tripped. When suction pressure drops below the LP switch cutout point, the contact opens and compressor 2 is shut down. This protects the compressor from operating in a vapor-starved condition that would result in overheating and mechanical failure.
Symptoms
- AL09 displayed on the Carel controller.
- Compressor 2 is shut down by the LP protection.
- Suction pressure on compressor 2's circuit is at or below the LP switch cutout pressure.
- Manual reset required after identifying and correcting the fault.
Common causes
- Refrigerant undercharge or leak causing insufficient suction pressure.
- Evaporator coil heavily iced over, blocking airflow and reducing evaporating pressure.
- Expansion valve stuck closed or thermostatic bulb charge lost.
- Suction line filter/dryer blocked, creating excessive pressure drop.
- LP pressure switch set too high relative to actual low-load operating conditions.
Ask the AskWhiz AI about Carel AL09
AskWhiz
online
Diagnostic steps
Measure suction pressure with gauges
Connect refrigerant gauges to compressor 2's suction service port. Confirm actual suction pressure is at or below the LP cutout setting.
Inspect the evaporator for ice buildup
Check the evaporator coil for icing. If iced over, initiate a manual defrost and check why defrost is not functioning correctly.
Check for refrigerant loss
Use an electronic leak detector to scan all refrigerant joints, valve stems, and brazed connections on compressor 2's circuit for leaks.
Check expansion valve operation
Verify the thermal expansion valve (or EEV) bulb is securely clamped to the suction line and insulated. An unclipped or failed bulb causes the valve to close fully, dropping suction pressure.
Reset the alarm after correction
After addressing the root cause, reset AL09 at the controller and monitor suction pressure for at least one full operating cycle before leaving the site.
When to call a professional
All refrigerant circuit work — leak detection with accurate electronic equipment, refrigerant recovery, recharge, and expansion valve replacement — requires F-Gas certification. Call a licensed refrigeration engineer. Do not reset and restart the compressor repeatedly without identifying the cause; operating a compressor with low suction pressure causes rapid oil and bearing damage.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com