AskWhiz
AL10Carel

Carel AL10

Compressor 1 LP in heating (pressure switch) Comp. 1 OFF Automatic Settable* AL1

Source: 030221501.pdf

Want this fix in your inbox? Full AL10 guide + every Carel code, printable, free.

What does Carel AL10 mean?

AL10 on Carel µChiller and pCO chiller controllers signals that the low-pressure (LP) safety switch on compressor 1's heating circuit has tripped. In heat-pump mode, the LP switch monitors suction pressure on the heating cycle; if it drops too low, compressor 1 is shut down to prevent operation in a vapor-starved condition during low outdoor temperature heating operation.

Symptoms

  • AL10 displayed on the Carel controller.
  • Compressor 1 is shut down during heating operation.
  • Suction pressure on compressor 1's circuit is at or below the LP cutout in heating mode.
  • Alarm requires manual reset after diagnosis.

Common causes

  • Outdoor ambient temperature too low for the heat pump's rated operating range.
  • Refrigerant undercharge causing low suction pressure even in heating mode.
  • Outdoor coil (acting as evaporator in heating mode) heavily iced over, blocking airflow.
  • Outdoor fan motor failed, reducing airflow over the outdoor coil.
  • LP switch cutout pressure set too high relative to low-ambient heating conditions.

Diagnostic steps

  1. 01

    Record the outdoor ambient temperature

    Check the current outdoor temperature against the unit's rated minimum heating ambient. Operating below the minimum rating causes LP trips in heating mode.

  2. 02

    Inspect the outdoor coil for ice

    Check the outdoor coil for ice bridging or heavy frost that blocks airflow. Initiate a defrost cycle if icing is present and investigate why defrost did not clear it automatically.

  3. 03

    Verify outdoor fan operation

    Confirm the outdoor fan is running at correct speed. A failed fan motor starves the outdoor coil of airflow, dropping evaporating pressure in heating mode.

  4. 04

    Connect refrigerant gauges and check suction pressure

    Measure suction pressure on compressor 1's circuit in heating mode. Compare to expected saturation pressure for the current outdoor temperature.

  5. 05

    Reset the alarm after correction

    After addressing the identified cause, reset AL10 at the controller and monitor the system through a full heating cycle.

Keep this fix — get it by email with every Carel error code

A clean printable version of this Carel AL10 guide + the full Carel code pack (130 codes), straight to your inbox. Free.

I am a — required, one click

When to call a professional

Call a licensed refrigeration/heat pump engineer for refrigerant handling, recharge, LP switch replacement, or investigation of LP trips occurring at ambient temperatures within the unit's rated operating range. These indicate refrigerant circuit or control faults that are unsafe to diagnose without proper tools and F-Gas certification.

Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.

Open a ticket — free account

Other Carel error codes

Sources: www.carel.com, www.carel.com