Carel AL11 Error Code
High room temperature See T2 AL12 AL13 Low room temperature High ambient humidit
Source: 030221426.pdf
What does Carel AL11 mean?
AL11 is the High Room Temperature alarm on the Carel Standard Air-conditioner (030221426). The room temperature probe reading has exceeded the high-temperature alarm threshold (setpoint plus the configured high alarm offset) for the required detection period. The unit remains operational but signals that cooling is inadequate for the current heat load.
Symptoms
- AL11 displayed on the controller with buzzer active.
- Room temperature reading above the high alarm limit.
- Cooling compressors are running but unable to reach the temperature setpoint.
- No equipment shutdown occurs — this is a display and relay notification alarm.
Common causes
- Cooling capacity insufficient for the actual heat load in the room.
- Refrigerant charge low, reducing compressor capacity.
- Condenser or chilled water coil fouled, reducing heat rejection.
- High ambient temperature reducing chiller efficiency below required output.
- High alarm offset set too small, triggering nuisance alarms during normal recovery.
Ask the AskWhiz AI about Carel AL11
AskWhiz
online
Diagnostic steps
Verify the unit is running at full cooling capacity
Confirm both compressors (if dual-circuit) are running and the cooling valve is at the required position. An alarm or fault on a compressor may have reduced capacity without a separate notification.
Check the high alarm offset parameter
In the service menu, review the high alarm offset (T2). If set too close to the setpoint differential, normal temperature recovery after a peak load causes spurious AL11 events.
Inspect the condenser or chilled water circuit
Check condenser coils for fouling or low airflow. On chilled-water units, verify chilled water supply temperature and flow are within design specifications.
Assess room heat load
Check for unusual heat sources — additional IT equipment, blocked air return paths, or open doors — that may have increased the heat load beyond the unit's rated capacity.
When to call a professional
Engage a refrigeration technician if the high-temperature condition persists with all equipment confirmed operational. Low refrigerant charge diagnosis and correction, compressor capacity testing, and heat load analysis require specialized instruments and refrigerant handling certification.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.it