Carel AL12 Error Code
AL13 Compressor 2 LP in heating (pressure switch) Compressor 1 maintenance Compr
Source: 030221501.pdf
What does Carel AL12 mean?
AL12 on the Carel Standard Roof-top controller (program code +030221501, running on pCO1/pCO3/pCOxs hardware) indicates that the high-pressure safety switch on circuit 1 has opened. The controller immediately stops compressor 1 and locks circuit 1 off until a manual reset is performed. The alarm protects the compressor from operating at discharge pressures that would exceed its safe design limits.
Symptoms
- AL12 is displayed on the pCO terminal with circuit 1 compressor(s) stopped immediately.
- High-side (discharge) pressure on circuit 1 was at or above the high-pressure cutout setting when the switch opened.
- Manual alarm reset is required — the alarm does not clear automatically.
- Cooling capacity from circuit 1 is lost until the alarm is reset and the root cause is corrected.
- The alarm relay activates and the buzzer sounds.
Common causes
- Condenser fouled with dirt, debris, or grease reducing heat rejection and driving up discharge pressure.
- Condenser fans not running at full speed or stopped — motor failure, thermal overload trip, or inverter fault.
- Refrigerant overcharge causing excessive liquid volume and elevated condensing pressure.
- Outdoor ambient temperature temporarily very high combined with inadequate airflow around the unit.
- High-pressure cutout switch calibration has drifted, causing premature tripping below the design threshold.
- Blocked or partially closed discharge service valve restricting flow.
Ask the AskWhiz AI about Carel AL12
AskWhiz
online
Diagnostic steps
Identify and correct the root cause before resetting
Before pressing the alarm reset key, confirm that the high-pressure condition has resolved. Resetting into an uncleared fault will cause the compressor to trip again immediately and risks damaging the cutout switch from repeated cycling.
Inspect the condenser section
Check all condenser fans are running and blowing air in the correct direction. Inspect coil surfaces for fouling. A blocked coil is the most common cause of high-pressure trips in warm weather — clean the coil from the inside out with compressed air or fin-cleaning solution.
Check discharge-side isolation valves
Confirm that no service valves on the high-pressure side of circuit 1 are partially closed. A partially closed valve restricts refrigerant flow and causes rapid pressure build-up.
Verify the high-pressure cutout switch setting
Using a manifold gauge set on circuit 1, confirm the actual discharge pressure when the switch opened. Compare to the factory cutout setting (typically 28–32 bar for HFC refrigerants). If the switch tripped well below its rated setting, the switch may need replacement.
Manually reset AL12 on the controller
Once the root cause is resolved, press the Alarm button on the pCO terminal to display AL12, then press it again to reset. If the high-pressure condition has cleared, circuit 1 will restart after the configured minimum off-time has elapsed.
When to call a professional
Call a licensed refrigeration engineer if AL12 recurs after cleaning the condenser and confirming fans are operational, or if you suspect refrigerant overcharge, a defective high-pressure switch, or a refrigerant circuit restriction. Handling refrigerant — including checking charge or replacing components — requires F-Gas certification. A technician should also verify that the high-pressure cutout switch meets the system's safety requirements before leaving the unit in service.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
5 free questions per bot in your browser — no signup.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.manualslib.com
AskWhiz Playground
Test your diagnostic skills
Play a real HVAC service call in the AskWhiz Playground — real brands, real fault codes, no signup.
Play a real service call