Carel AL16 Error Code
Energy meter 12 offine Automatic No YES AL17 ProbeB1fault Automatic No YES AL18
Source: 040000131.pdf
What does Carel AL16 mean?
AL16 on the Carel pLoads load management controller means Energy Meter 12 (the twelfth energy meter on the Modbus RS485 network at address 13) has gone offline or lost communication. The pLoads controller polls all configured energy meters on a regular cycle. When a meter fails to respond within the configured timeout, AL16 fires and the alarm relay activates. Load cut-off functions that depend on this meter's data are not affected unless it is the primary metering device.
Symptoms
- AL16 displayed on the pLoads pGD1 terminal with the alarm relay energized
- Energy Meter 12 data frozen or absent on the supervisor communication variables
- No impact on other energy meters unless inter-meter dependencies are configured
Common causes
- RS485 communication cable break or loose termination between pLoads and Energy Meter 12
- Energy Meter 12 has lost power or failed internally
- Modbus address conflict — another device incorrectly assigned address 13
- Communication timeout parameter set too short for the cable length or network conditions
Ask the AskWhiz AI about Carel AL16
AskWhiz
online
Diagnostic steps
Check RS485 wiring to Energy Meter 12
Trace the RS485 cable from the pLoads FieldBus port to Energy Meter 12. Inspect for breaks, loose terminal screws, and correct polarity (A/B wiring). Verify the cable is terminated with the correct termination resistor if it is the last device.
Verify Energy Meter 12 power supply
Confirm Energy Meter 12 has its rated power supply voltage at its power terminals. A blown fuse or tripped breaker upstream of the meter cuts communication immediately.
Confirm Modbus address assignment
Verify Energy Meter 12 is programmed to Modbus address 13 using its front panel DIP switches or configuration software. Address conflicts cause the meter to fail to respond to pLoads polls.
Test RS485 communication with pCO Manager
Connect a laptop with CAREL pCO Manager via the USB slave port and poll the FieldBus serial line for devices at address 13. No response confirms a physical or address configuration fault.
Adjust communication timeout if needed
In the pLoads energy meter setup screens, increase the Modbus communication timeout parameter. Long cable runs or RB Router Bridge networks need extended timeouts to avoid false offline alarms.
When to call a professional
If Energy Meter 12 does not respond after wiring and address verification, the meter unit itself may have failed and requires replacement. RS485 network issues affecting multiple devices simultaneously indicate a wiring or termination problem that benefits from a trained controls technician with a Modbus protocol analyzer.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com