Carel AL17
Heaters off Manual No Settable AL18 Heater1and 2overload Flow switch alarm Unit
Source: 030221501.pdf
What does Carel AL17 mean?
AL17 on Carel µChiller and pCO chiller controllers signals that the electric heaters have been commanded off by an active alarm condition. In configurations where auxiliary electric heaters are used for anti-freeze protection or heat-pump supplementary heating, AL17 activates when a safety input (such as a heater thermal cutout or a configurable digital input alarm) opens and forces the heater output off. The alarm is manual-reset.
Symptoms
- AL17 displayed on the Carel controller.
- Electric heater outputs are de-energized.
- Anti-freeze or supplementary heating is unavailable.
- Manual reset required after the alarm condition is resolved.
Common causes
- Heater thermal cutout (safety thermostat) tripped due to heater overtemperature.
- Heater thermal overload relay tripped due to excessive current draw.
- Digital input configured as heater alarm interlock has opened.
- Controller parameter configuration incorrectly enabling AL17 from an unrelated digital input.
Diagnostic steps
- 01
Locate the heater section and inspect for overtemperature
Open the heater assembly access panel and check the heater elements and safety thermostat for signs of overheating — discoloration, burning smell, or visibly damaged elements.
- 02
Reset the heater thermal cutout
If the heater thermal cutout has tripped, allow the heater to cool for 15 minutes, then press the manual reset button on the cutout device.
- 03
Check the heater thermal overload relay
Inspect the motor control panel for the heater overload relay. If tripped, reset it and measure heater running current to confirm it is within nameplate rating.
- 04
Verify the alarm interlock digital input
Identify which digital input drives the AL17 alarm on this controller. Check the wiring and the physical device connected to confirm the contact has re-closed after the fault resolved.
- 05
Reset AL17 at the controller
After corrective action, perform a manual reset of AL17 at the Carel controller and verify heater outputs re-energize as expected.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL17 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
Contact a licensed electrician or refrigeration engineer if heater elements are visibly damaged, if the thermal cutout trips immediately after reset, or if current measurements show the heater is drawing well above rated current. Electric heater circuits operate at full mains voltage and high current; repairs require proper isolation and electrical qualifications.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com