Carel AL19 Error Code
Clockboard fault or absent Manual Settable Display only Cool set point less than
Source: 030221501.pdf
What does Carel AL19 mean?
AL19 on Carel µChiller and pCO chiller controllers indicates a clockboard fault or absence. The controller relies on the real-time clock (RTC) module for time-scheduled operations such as night setback, timed defrost, and maintenance hour counters. When the RTC is absent or has failed, AL19 activates. The alarm is display-only in most configurations but disables all time-based scheduling functions.
Symptoms
- AL19 displayed on the Carel controller.
- Time-based scheduling functions — night setback, timed defrost — are unavailable.
- The controller clock shows incorrect or frozen time.
- Maintenance hour counters may not advance correctly.
Common causes
- RTC module (clock board) not installed or has become unseated from its socket.
- RTC backup battery dead, causing the clock to reset after every power cycle.
- RTC chip or clock board hardware failure.
- Controller firmware incompatibility with the installed clock module version.
Ask the AskWhiz AI about Carel AL19
AskWhiz
online
Diagnostic steps
Inspect the RTC module installation
With power off, open the controller and verify the clock board is correctly seated in its socket. Re-seat if it appears loose or displaced.
Replace the RTC backup battery
Locate the coin cell battery on the clock board. A flat battery causes the clock to reset on every power cut. Replace with the same specification cell (typically CR2032).
Reset the date and time
After battery replacement, set the correct date and time in the controller's clock menu and verify the settings are retained after a power cycle.
Check for clock board hardware failure
If the clock board is seated and the battery is good but AL19 persists, the clock board itself may be faulty. Order a replacement Carel RTC module for the specific controller model.
Reset AL19 at the controller
After fitting a working clock board, reset AL19 and verify scheduled functions resume correctly.
When to call a professional
Contact a Carel-authorized service engineer if the clock board part number is unknown or if replacing it requires controller disassembly beyond standard access. An engineer with Carel tooling can also reflash controller firmware if a compatibility issue between controller software and clock hardware is suspected.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com