Carel AL260
AL261 High Pressure alarm 1 High Pressure alarm 2 Auto Auto Fc03 Fc03
Source: 0300081EN.pdf
What does Carel AL260 mean?
AL260 is a High Pressure alarm 1 on the Carel µChiller system. The refrigerant high-pressure switch or pressure transducer on circuit 1 has detected that discharge pressure has exceeded the safety limit. The controller shuts down circuit 1 compressors immediately to prevent damage to the compressor, condenser, and refrigerant piping.
Symptoms
- Circuit 1 compressors shut down immediately on alarm activation.
- AL260 displayed on controller with buzzer and Alarm LED active.
- Discharge pressure above the high-pressure switch trip point.
- Manual reset required to restart the circuit in most configurations.
Common causes
- Condenser coils fouled with dirt, scale, or debris reducing heat rejection.
- Condenser fan failed or running at reduced speed.
- Refrigerant overcharge increasing condensing pressure.
- Non-condensable gases (air) trapped in the refrigerant circuit.
- High ambient temperature pushing condensing pressure above the pressure switch set point.
Diagnostic steps
- 01
Identify and eliminate the high-pressure condition before reset
Do not reset the alarm while the condition persists. Allow the system to equalize and identify the root cause before re-energizing compressors.
- 02
Inspect and clean the condenser
Check condenser coils or cooling tower for fouling. Clean air-cooled coils by blowing out debris or washing, depending on the condenser type. Fouled condensers are the most common high-pressure cause.
- 03
Verify condenser fan operation
Confirm all condenser fans are running at rated speed with correct rotation. A failed or reversed fan significantly reduces heat rejection and raises head pressure.
- 04
Check for non-condensables
Connect service gauges to the high-side. If discharge pressure is abnormally high relative to the ambient saturation temperature for the refrigerant, non-condensable gas contamination is likely. Recover refrigerant, evacuate, and recharge.
- 05
Manually reset the alarm and monitor
After correcting the root cause, manually reset AL260 on the controller. Monitor discharge pressure for 15 minutes after restart to confirm stable operation below the alarm threshold.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL260 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
A licensed technician is required for refrigerant recovery, non-condensable purging, and recharge. If the high-pressure alarm trips repeatedly despite a clean condenser and properly operating fans, a refrigerant charge assessment, pressure switch calibration check, or compressor valve inspection is needed — all of which require specialized refrigeration tools and certifications.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, docs.quecalor.com