What does Carel AL27 mean?
AL27 is the Built-in Humidifier High Current alarm on the Carel Standard Air-conditioner (030221426). The integrated steam humidifier has drawn more current than its rated limit, indicating either a scale-blocked cylinder allowing excessive conductivity between the electrodes, or an electrical fault. The humidifier disables on this alarm to prevent overloading the supply circuit.
Symptoms
- Built-in humidifier stops producing steam and is disabled.
- AL27 displayed on the controller.
- Humidifier cylinder may have visible heavy scale buildup on the electrodes.
- Circuit breaker feeding the humidifier may trip on severe overcurrent.
Common causes
- Heavy scale buildup between electrodes increasing water conductivity and current draw.
- Supply water conductivity too high for the cylinder configuration.
- Partially short-circuited cylinder from scale bridging between electrode surfaces.
- Incorrect cylinder type installed — higher-capacity cylinder drawing more current than rated.
- Electrical wiring fault causing an external current path.
Diagnostic steps
- 01
Inspect the humidifier cylinder for scale
Remove the humidifier cylinder and inspect electrode surfaces for heavy scale or bridging between electrodes. Scale deposits significantly increase water conductivity, driving current above the limit.
- 02
Clean the cylinder and electrodes
Follow the manufacturer descaling procedure for the cylinder type. For openable cylinders, clean electrode surfaces and the cylinder wall. For disposable cylinders, replace if heavily scaled.
- 03
Check supply water conductivity
Measure the conductivity of the incoming water supply with a conductivity meter. Water conductivity above the rated range for the cylinder causes chronically high current. A water treatment or dilution system may be required.
- 04
Verify the correct cylinder type is installed
Confirm the cylinder model number matches the controller configuration. An oversized cylinder for the unit's power rating draws excessive current from the start.
- 05
Restart and monitor current
After cleaning or replacing the cylinder, restart the humidifier and monitor current draw for the first fill cycle. Current should be within the rated limit for the configured cylinder capacity.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL27 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
Contact a Carel service technician if AL27 returns immediately after cylinder replacement with correctly rated components, or if a wiring short circuit is suspected. Electrical fault investigation inside the precision air conditioning unit requires qualified electrical personnel.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.it