Carel AL27 Error Code
AL28 Built-in humidifier: high current Built-in humidifier: no water in the cyli
Source: 030221426.pdf
What does Carel AL27 mean?
AL27 is the Built-in Humidifier High Current alarm on the Carel Standard Air-conditioner (030221426). The integrated steam humidifier has drawn more current than its rated limit, indicating either a scale-blocked cylinder allowing excessive conductivity between the electrodes, or an electrical fault. The humidifier disables on this alarm to prevent overloading the supply circuit.
Symptoms
- Built-in humidifier stops producing steam and is disabled.
- AL27 displayed on the controller.
- Humidifier cylinder may have visible heavy scale buildup on the electrodes.
- Circuit breaker feeding the humidifier may trip on severe overcurrent.
Common causes
- Heavy scale buildup between electrodes increasing water conductivity and current draw.
- Supply water conductivity too high for the cylinder configuration.
- Partially short-circuited cylinder from scale bridging between electrode surfaces.
- Incorrect cylinder type installed — higher-capacity cylinder drawing more current than rated.
- Electrical wiring fault causing an external current path.
Ask the AskWhiz AI about Carel AL27
AskWhiz
online
Diagnostic steps
Inspect the humidifier cylinder for scale
Remove the humidifier cylinder and inspect electrode surfaces for heavy scale or bridging between electrodes. Scale deposits significantly increase water conductivity, driving current above the limit.
Clean the cylinder and electrodes
Follow the manufacturer descaling procedure for the cylinder type. For openable cylinders, clean electrode surfaces and the cylinder wall. For disposable cylinders, replace if heavily scaled.
Check supply water conductivity
Measure the conductivity of the incoming water supply with a conductivity meter. Water conductivity above the rated range for the cylinder causes chronically high current. A water treatment or dilution system may be required.
Verify the correct cylinder type is installed
Confirm the cylinder model number matches the controller configuration. An oversized cylinder for the unit's power rating draws excessive current from the start.
Restart and monitor current
After cleaning or replacing the cylinder, restart the humidifier and monitor current draw for the first fill cycle. Current should be within the rated limit for the configured cylinder capacity.
When to call a professional
Contact a Carel service technician if AL27 returns immediately after cylinder replacement with correctly rated components, or if a wiring short circuit is suspected. Electrical fault investigation inside the precision air conditioning unit requires qualified electrical personnel.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.it