Carel AL30 Error Code
Heater 1 thermal overload Heater 2 thermal overload (if ambient temp. probe) 60
Source: 030221501.pdf
What does Carel AL30 mean?
AL30 on Carel µChiller and pCO chiller controllers indicates that the thermal overload protection device on one or both electric heaters (heater 1 or heater 2) has tripped due to overcurrent. This protection prevents heater element burnout when the heater draws more current than its rated value. The alarm requires manual reset after the heater cools down and the fault cause is identified.
Symptoms
- AL30 displayed on the Carel controller.
- Heater 1 or heater 2 output is de-energized.
- Anti-freeze or supplementary electric heating is unavailable.
- The thermal overload relay in the heater circuit has tripped.
Common causes
- Heater element partially failed, causing unbalanced current draw.
- Supply voltage too high, increasing heater current above rated value.
- Thermal overload relay sized incorrectly for the installed heater element rating.
- Heater operating in a poorly ventilated space causing thermal overload of the overload relay itself.
Ask the AskWhiz AI about Carel AL30
AskWhiz
online
Diagnostic steps
Allow the heater and overload relay to cool
Wait at least 15 minutes before attempting to reset. Thermal overload relays require cooling before they will reset.
Inspect the heater element
With power isolated, visually inspect the heater element for burn marks, discoloration, or physical damage that indicates an element failure.
Measure heater element resistance
Disconnect the heater element and measure resistance across each element. Infinite resistance (open circuit) or zero resistance (short) confirms element failure.
Check supply voltage
Measure supply voltage at the heater terminals. Overvoltage (more than 10% above rated) increases heater current proportionally.
Reset the overload relay and AL30
After cooling and corrective action, reset the thermal overload relay manually in the panel, then reset AL30 at the Carel controller.
When to call a professional
Call a licensed electrician if the heater element requires replacement, if supply voltage is found out of tolerance, or if the overload relay trips immediately on restart. Working on heater circuits involves exposure to mains voltage and must be performed under proper isolation procedures by qualified personnel.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com