Carel AL31 Error Code
Manual No AL32 Minor alarm from digital input Manual No AL33 Compressor3thermalo
Source: 030221501.pdf
What does Carel AL31 mean?
AL31 on Carel µChiller and pCO chiller controllers is a minor alarm generated from a configurable digital input. Unlike AL29, this alarm does not shut down the unit — it activates a display-only warning or a low-priority alarm output. The digital input is typically wired to a non-critical monitoring device such as a filter differential pressure switch, a maintenance reminder switch, or an auxiliary sensor.
Symptoms
- AL31 displayed on the Carel controller.
- Unit continues to operate normally; no compressor or output shutdown.
- The device connected to the AL31 digital input has opened its contact.
- Alarm is a reminder or advisory — not a safety shutdown.
Common causes
- Non-critical monitoring device (filter switch, auxiliary sensor) has signaled a fault or maintenance condition.
- Wiring to the AL31 digital input is broken or disconnected.
- Device connected to the input has failed open-circuit.
- Configuration error or an incorrect device assigned to this minor alarm input.
Ask the AskWhiz AI about Carel AL31
AskWhiz
online
Diagnostic steps
Identify the device wired to AL31
Consult the site wiring diagram to determine what device drives the AL31 input — it is often a filter differential pressure switch or a maintenance contact.
Check the physical device for a real condition
Inspect the referenced device. If it is a filter switch, check the filter for clogging. If it is a maintenance switch, verify whether a maintenance interval has elapsed.
Inspect AL31 terminal wiring
Check the digital input wiring at both the controller terminal and the device end. Look for loose screws, broken conductors, or corroded contacts.
Address the underlying condition
If the alarm is from a dirty filter, replace or clean the filter. If it is a maintenance reminder, perform the required maintenance and reset the counter.
Reset AL31 at the controller
Once the digital input contact has re-closed after the condition is resolved, reset AL31 manually at the controller.
When to call a professional
Although AL31 is a minor alarm, the device connected to the input should always be investigated to rule out a developing fault. If the source device is a refrigerant detector or a safety device that has been incorrectly wired to the minor alarm input rather than AL29, contact a refrigeration engineer immediately to review the wiring and alarm configuration.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com