Carel AL36 Error Code
Operating hour threshold reached forhumidifier AL37 High pressure + compressor 2
Source: 030221426.pdf
What does Carel AL36 mean?
AL36 is the Built-in Humidifier Operating Hour Threshold alarm on the Carel Standard Air-conditioner (030221426). The integrated humidifier has accumulated the configured number of operating hours since the last maintenance reset, signaling that scheduled maintenance — cylinder inspection, cleaning, or replacement — is due. This is a warning alarm; the humidifier continues to operate.
Symptoms
- AL36 displayed on the controller as a maintenance warning.
- Humidifier continues operating normally — no shutdown occurs.
- Hour counter has reached the programmed maintenance threshold.
- Alarm relay may activate per configured alarm relay assignment.
Common causes
- Humidifier has reached the programmed operating hour maintenance interval.
- Hour counter was not reset at the previous maintenance service.
- High water conductivity or poor water quality accelerating scale buildup, making more frequent service necessary.
Ask the AskWhiz AI about Carel AL36
AskWhiz
online
Diagnostic steps
Inspect the humidifier cylinder
Remove and inspect the cylinder electrodes for scale buildup. Heavily scaled electrodes require cleaning or cylinder replacement even if the unit is still producing steam.
Clean or replace the cylinder
For openable cylinders, descale using the procedure in the service manual. For disposable cylinders with significant electrode wear or heavy scale, replace with a new cylinder.
Inspect the drain valve and level sensor
Clean the drain valve seat and strainer. Remove and clean the conductivity electrodes on the level sensor assembly to ensure accurate water level control.
Reset the hour counter parameter
After completing maintenance, navigate to the hour counter reset parameter in the controller programming menu and reset it. AL36 will not clear until the counter is reset manually.
When to call a professional
Contact a qualified HVAC technician if the humidifier shows AL36 together with active alarms such as high current, drain failure, or fill failure, indicating a more serious maintenance condition. If hour intervals are shorter than expected due to poor water quality, a water treatment specialist should assess the supply water chemistry.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.it