Carel AL40
No water flow See T4 yes All AL41 pLAN disconnected 60 s (fixed) AL42 Driver 1 p
Source: 030221426.pdf
What does Carel AL40 mean?
AL40 is the No Water Flow alarm on the Carel Standard Air-conditioner (030221426). The water flow switch on a chilled-water or condenser water circuit has opened, indicating insufficient or zero flow. The controller shuts down all cooling to prevent evaporator freezing or condenser overheating without adequate water flow.
Symptoms
- All compressors and the cooling valve shut down immediately.
- AL40 displayed on the controller with alarm notification.
- Water flow switch in the chilled water or condenser water circuit is open.
- Water pump may still be running but flow is absent or below the switch threshold.
Common causes
- Water pump failed or not running.
- Air lock in the piping circuit preventing flow.
- Closed isolation valve or ball valve in the water circuit.
- Blocked strainer on the water pump suction side.
- Flow switch set too high or flow switch has failed open.
Diagnostic steps
- 01
Confirm water pump operation
Verify the pump is energized, running in the correct direction, and not tripped on overload. Check the pump electrical panel for any fault indication.
- 02
Check and open all isolation valves
Inspect all ball valves and isolation valves in the water circuit. A single closed valve blocks flow through the entire circuit and trips the flow switch.
- 03
Bleed air from the water circuit
Open the air vent at the highest point in the water circuit. Purge air until a steady water stream flows and close the vent. Air pockets reduce effective flow below the switch threshold.
- 04
Clean the pump strainer
Close isolation valves around the strainer, remove the basket, and clear any debris or scale. Reinstall the basket and open isolation valves before restarting the pump.
- 05
Test the flow switch
Confirm flow is present by other means (flow meter, pump current), then check switch continuity. Replace the switch if it remains open during confirmed adequate flow.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL40 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
Contact a plumbing or mechanical contractor if the water circuit requires flushing, pressure testing, or chemical cleaning for biological contamination or scale. A refrigeration technician should evaluate the unit if AL40 persists with confirmed adequate flow, suggesting a faulty flow switch or controller input card fault.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.it