Carel AL41 Error Code
Driver1EEPROMerror No AL42 Driver2EEPROMerror Driver 1 EEVmotor error Circuit 2
Source: 030221501.pdf
What does Carel AL41 mean?
AL41 on Carel µChiller and pCO chiller controllers indicates an EEPROM error on EEV driver 1 (the electronic expansion valve driver for circuit 1). The EVD driver stores calibration and configuration data in its internal EEPROM memory. When this memory is corrupted or unreadable, AL41 activates and circuit 1 EEV control is disabled, preventing the driver from operating the valve in automatic superheat control mode.
Symptoms
- AL41 displayed on the Carel controller.
- Circuit 1 EEV driver is not controlling superheat; the valve may default to a fixed position.
- Refrigerant superheat on circuit 1 is unregulated.
- No automatic reset is possible; the driver requires attention.
Common causes
- EEV driver 1 EEPROM chip corrupted by a power surge or voltage spike.
- EEPROM chip at end of write-cycle life from excessive parameter changes.
- EEV driver 1 board hardware failure.
- Loss of supply power to the driver during a firmware write operation.
Ask the AskWhiz AI about Carel AL41
AskWhiz
online
Diagnostic steps
Power-cycle the EEV driver
Switch off power to EVD driver 1, wait 30 seconds, then restore power. A transient fault may clear on re-initialization.
Check driver supply voltage
Measure supply voltage at the EVD driver 1 terminals. Voltage spikes or low voltage during parameter saves corrupt EEPROM data.
Re-enter driver parameters if possible
If the driver initializes but shows default values after the power-cycle, re-enter all EVD driver 1 parameters (refrigerant type, valve model, superheat setpoints) using the Carel configuration tool or controller interface.
Check firmware version compatibility
Confirm that the EEV driver firmware version is compatible with the chiller controller software version. Mismatched versions can cause memory initialization failures.
Replace the EVD driver if EEPROM is permanently damaged
If AL41 returns after parameter re-entry, the EEPROM is beyond recovery. Replace the Carel EVD driver 1 with a compatible replacement unit.
When to call a professional
EVD driver replacement and re-commissioning — including refrigerant type selection, valve model configuration, and superheat setpoint adjustment — requires a refrigeration engineer familiar with Carel EEV systems. Incorrect EVD configuration causes refrigerant liquid slugging or compressor overheating, both of which cause catastrophic compressor damage.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com