Carel AL43 Error Code
AL44 Driver 2 EEVmotor error Driver 1 MOP timeout Circuit 2 off Manual 10 S AL45
Source: 030221501.pdf
What does Carel AL43 mean?
AL43 on Carel µChiller and pCO chiller controllers indicates that EEV driver 2's expansion valve motor has a fault. The Carel EVD driver monitors motor current during valve stepping operations; if the motor fails to respond correctly — due to an open winding, a mechanical jam, or a wiring break — the driver raises this alarm. Circuit 2 EEV control is disabled, removing automatic superheat regulation for that circuit.
Symptoms
- AL43 displayed on the Carel controller.
- Circuit 2 EEV valve motor is not responding to step commands.
- Superheat on circuit 2 is uncontrolled.
- Circuit 2 may shut down depending on the alarm response configuration.
Common causes
- Broken coil wire inside the EEV valve motor causing an open winding.
- EEV wiring harness connector between the driver and valve loose or disconnected.
- EEV motor jammed mechanically due to debris or excessive scale in the valve seat.
- EEV driver 2 output stage hardware failure.
Ask the AskWhiz AI about Carel AL43
AskWhiz
online
Diagnostic steps
Check the EEV valve wiring harness
Inspect the 4-wire or 6-wire cable from EVD driver 2 to the EEV valve. Look for broken conductors, damaged connectors, or connector pins backed out of the housing.
Measure EEV motor winding resistance
Disconnect the valve from the driver and measure each motor winding resistance using the valve manufacturer's specification. Open windings read infinite resistance; confirm against expected values (typically 40–200 Ω per winding depending on valve model).
Power-cycle the EVD driver 2
Switch off the driver, wait 30 seconds, and restore power. The driver will attempt a valve re-homing sequence on startup. Listen or feel for valve movement.
Manually command the valve through a full stroke
Using the EVD driver's manual mode or the controller service menu, command the valve fully open then fully closed. Resistance or stuttering indicates a mechanical or electrical fault in the valve.
Replace the EEV valve if windings are open or motor is jammed
Install a compatible Carel EEV valve with the correct valve model for the refrigerant and system capacity.
When to call a professional
EEV replacement requires recovery of refrigerant from the affected circuit before removing the valve and brazing in a replacement — all operations requiring an F-Gas certified engineer. An uncorrected AL43 on circuit 2 causes loss of superheat control and risks compressor damage from liquid flood-back.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com