Carel AL46 Error Code
Manual Manual 10 s No AL47 Driver2LOPtimeout Circuit 1 off No AL48 Driver 1 low
Source: 030221501.pdf
What does Carel AL46 mean?
AL46 on Carel µChiller and pCO chiller controllers indicates that EEV driver 2 has exceeded the Low Operating Pressure (LOP) timeout. The Carel EVD driver's LOP protection opens the expansion valve when evaporating temperature drops too low, preventing the compressor from operating in a liquid-starved, excessively low-pressure condition. When evaporating temperature stays below the LOP limit longer than the permitted timeout, AL46 activates and circuit 1 is shut off.
Symptoms
- AL46 displayed on the Carel controller.
- Circuit 1 is shut down following a LOP timeout.
- Evaporating temperature on circuit 1 was running abnormally low.
- Suction pressure is below normal for the current operating conditions.
Common causes
- Refrigerant undercharge causing insufficient suction pressure and excessively low evaporating temperature.
- EEV valve stuck closed or failing to open, starving the evaporator of refrigerant.
- Suction line filter/dryer partially blocked, restricting refrigerant flow.
- EVD driver 2 LOP setpoint configured too close to normal operating conditions.
Ask the AskWhiz AI about Carel AL46
AskWhiz
online
Diagnostic steps
Connect refrigerant gauges to circuit 1 suction
Verify actual suction pressure and convert to saturation temperature for the refrigerant type. Confirm whether the evaporating temperature is genuinely below the LOP limit.
Check for refrigerant undercharge
Inspect the system for refrigerant leaks using an electronic leak detector at all joints, valve stems, and brazed connections on circuit 1.
Test EEV valve operation
Using the EVD driver 2 manual mode, fully open the EEV valve and observe whether suction pressure rises. If pressure stays low with the valve fully open, refrigerant charge or a filter blockage is the cause.
Inspect the suction filter/dryer
Check the moisture indicator sight glass on the suction dryer. Replace a discolored (yellow/brown) dryer and investigate moisture ingress if indicated.
Review LOP setpoint in EVD driver 2
Verify the LOP setpoint (evaporating temperature) is correct for this refrigerant and application. Adjust if it is set too high relative to normal low-load operating conditions.
When to call a professional
Refrigerant leak detection, recharge, and dryer replacement on a live refrigerant circuit all require F-Gas certification. Contact a licensed refrigeration engineer. Do not restart circuit 1 repeatedly with a suspected undercharge; operating a compressor in a vapor-starved condition causes rapid compressor oil carbonization and bearing failure.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com