Carel AL48
Driver 1 low superheat See F9 Compressor 1 AL49 Driver 1 valve not closed during
Source: 030221426.pdf
What does Carel AL48 mean?
AL48 on Carel µChiller and pCO chiller controllers indicates that EEV driver 1 has detected a low superheat condition. The Carel EVD driver monitors refrigerant superheat at the compressor suction and activates low superheat protection when measured superheat drops below the configured minimum threshold. AL48 causes circuit 1 to be shut down to prevent liquid refrigerant from entering the compressor.
Symptoms
- AL48 displayed on the Carel controller.
- Circuit 1 is shut down by the EEV driver low superheat protection.
- Suction line and compressor suction pipe may be frosting or sweating heavily.
- Superheat measured by the EVD driver was below the minimum setpoint.
Common causes
- Refrigerant overcharge causing excessive liquid in the evaporator and low superheat.
- EEV valve oversized for the system load, delivering more refrigerant than the evaporator can fully evaporate.
- Sudden load drop (e.g., hot gas bypass opening) causing evaporator to flood.
- Superheat sensor probe (suction pressure or temperature) incorrectly positioned or calibrated.
Diagnostic steps
- 01
Check suction line for signs of flooding
Inspect the compressor suction line for frost or heavy sweating extending back from the evaporator — evidence of liquid carry-over into the suction.
- 02
Verify refrigerant charge
Connect gauges and check suction pressure against the expected saturation temperature. High suction pressure relative to load conditions suggests overcharge.
- 03
Review EVD driver 1 superheat setpoint
Access the EVD driver 1 parameters and confirm the superheat setpoint is appropriate for the application — typically 5–8 K for most refrigerants in a chiller application.
- 04
Check the superheat sensors
Verify the suction temperature probe is correctly clamped to the suction line and insulated. An uninsulated probe reads ambient air temperature, producing falsely high superheat and causing the valve to over-open.
- 05
Reset AL48 after correction
After correcting the overcharge, valve sizing, or sensor issue, reset the alarm and monitor superheat through a complete operating cycle to confirm stability.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL48 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
Refrigerant charge adjustment requires F-Gas certification and must be performed by a licensed refrigeration engineer. An engineer should also evaluate whether the EEV valve model is correctly sized for the system — undersizing and oversizing both cause superheat instability that cannot be resolved by setpoint adjustment alone.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com