What does Carel AL50 mean?
AL50 on Carel µChiller and pCO chiller controllers indicates that EEV driver 2 detected that the expansion valve on circuit 2 was not fully closed when the system powered off. Like AL49, this is a valve position safety check performed at power-down. If the driver cannot complete the close sequence for the circuit 2 EEV, circuit 2 is locked out at the next startup to prevent compressor liquid slugging from an open valve.
Symptoms
- AL50 displayed on the Carel controller.
- Circuit 2 is locked out at startup following a power interruption or controlled shutdown.
- EEV driver 2 shows a valve position or power-off sequence fault.
- Manual reset required before circuit 2 can restart.
Common causes
- EEV valve 2 motor coil open or partially failed, preventing full close stroke.
- Mains power interrupted faster than the EVD driver 2 could complete its close sequence.
- EEV wiring harness on circuit 2 disconnected or intermittently open.
- EVD driver 2 energy storage insufficient to power the close sequence during power loss.
Ask the AskWhiz AI about Carel AL50
AskWhiz
online
Diagnostic steps
Inspect circuit 2 EEV wiring
Trace the wiring harness from EVD driver 2 to the circuit 2 expansion valve. Check for loose connectors, damaged insulation, or broken conductors.
Measure EEV valve 2 motor windings
Disconnect the EEV from EVD driver 2 and measure all winding resistances. Open or dramatically low resistance on any winding confirms motor failure requiring valve replacement.
Power-cycle EVD driver 2 and observe homing
Apply power to EVD driver 2 and observe whether it performs a valve homing sequence. If the valve fails to move, the winding measurement will confirm the cause.
Test valve operation in manual mode
Command the valve open and closed manually via the EVD driver 2 manual interface. Confirm the valve strokes smoothly through its full range before returning to automatic control.
Reset AL50 and verify normal operation
After confirming valve 2 functions correctly, reset AL50 at the controller. Restart circuit 2 and monitor superheat and suction pressure through the first operating cycle.
When to call a professional
EEV valve replacement on circuit 2 requires refrigerant recovery from that circuit before the valve can be removed, which requires F-Gas certification. Also contact a Carel-authorized engineer if AL50 recurs on a system that was properly powered down, as this indicates either intermittent valve motor winding faults or an EVD driver hardware problem requiring component diagnosis.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com, www.carel.com