Carel AL52 Error Code
AL53 Driver 1 high superheat Driver 2 high superheat Circuit 1 off Circuit 2 off
Source: 030221501.pdf
What does Carel AL52 mean?
AL52 indicates that Driver 1's electronic expansion valve (EEV) is operating in a sustained high-superheat condition. The refrigerant leaving the evaporator is exiting with more superheat than the controller's alarm threshold allows, which forces Circuit 1 offline to protect the compressor from overheating and potential damage.
Symptoms
- Circuit 1 shuts down and cannot be restarted until alarm is manually reset.
- Refrigerant suction temperature at compressor inlet is abnormally elevated.
- Evaporator capacity drops as the electronic expansion valve is not delivering adequate refrigerant flow.
- Controller display shows AL52 code with no automatic recovery.
Common causes
- Electronic expansion valve (EEV) on Driver 1 is stuck partially closed or mechanically blocked.
- Low refrigerant charge in the circuit, reducing mass flow through the evaporator.
- Pressure probe S1 reading incorrectly, causing the driver to miscalculate superheat.
- High load conditions exceeding the rated capacity of the evaporator.
- Loose or damaged wiring between the EEV driver and the valve motor.
Ask the AskWhiz AI about Carel AL52
AskWhiz
online
Diagnostic steps
Read the superheat value from Driver 1
Access the pCO controller menu and check the live superheat reading from Driver 1. Confirm the value is genuinely elevated rather than a sensor error.
Inspect the pressure probe (S1) and NTC temperature probe
Verify probe S1 connections and check for correct pressure readings. A faulty ratiometric transducer will produce false high superheat readings.
Check refrigerant charge on Circuit 1
Connect service gauges and verify suction and discharge pressures. Low suction pressure relative to saturation temperature confirms undercharge.
Inspect the EEV and driver wiring
Check the cable between Driver 1 and the expansion valve for continuity and correct pinout. Confirm the valve motor responds when commanded.
Manually reset the alarm
Once the underlying cause is corrected, manually reset AL52 from the controller alarm menu. AL52 requires manual reset and will not clear automatically.
When to call a professional
Call a licensed refrigeration technician if you confirm the expansion valve is mechanically blocked, if the refrigerant circuit requires recovery and recharge, or if the EEV driver board itself is faulty. Working with pressurized refrigerant systems requires EPA Section 608 certification, and replacing driver boards or valves involves energized high-voltage components.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com