Carel AL55 Error Code
Driver 2 high evaporation pressure (MOP) See Fj Compressor 2 AL56 Driver 2 low e
Source: 030221426.pdf
What does Carel AL55 mean?
AL55 is the Driver 2 High Evaporation Pressure (MOP) alarm on the Carel Standard Air-conditioner (030221426). The EVD driver on circuit 2 has detected that the evaporation temperature has remained above the MOP (Maximum Operating Pressure) threshold longer than the configured delay. The protector closes the expansion valve to reduce evaporation pressure and protect the compressor from overload.
Symptoms
- EVD driver 2 displays MOP protection active.
- AL55 on the controller display.
- Evaporation temperature on circuit 2 is above the MOP threshold.
- Compressor 2 may show elevated discharge temperature as the protector reduces refrigerant flow.
Common causes
- Refrigerant circuit 2 overcharged, causing abnormally high evaporation pressure.
- MOP protection threshold set below the actual rated evaporation temperature of the system.
- High heat load at start-up before circuit 2 reaches steady state.
- Expansion valve on circuit 2 not closing adequately, maintaining high evaporation pressure.
- Condenser on circuit 2 underperforming, raising system pressures.
Ask the AskWhiz AI about Carel AL55
AskWhiz
online
Diagnostic steps
Read evaporation temperature from EVD driver 2
Check the current evaporation temperature on the driver 2 display. Confirm it is genuinely above the MOP threshold, not a probe-related false reading.
Review MOP threshold on EVD driver 2
In the EVD driver 2 service menu, verify the MOP threshold is set above the system's rated evaporation temperature. A threshold set too low causes the protector to activate at normal operating pressures.
Enable MOP protection if disabled
Confirm the MOP integration time is greater than zero in the EVD driver 2 parameters. A zero value disables the protector, allowing high evaporation pressure to persist without correction.
Check refrigerant charge on circuit 2
Connect service gauges to circuit 2. High suction pressure relative to ambient saturation temperature indicates refrigerant overcharge. Partial recovery by a certified technician is required.
Stagger start-up sequence for circuits
If MOP alarms occur consistently at start-up, configure circuit 2 to start at least 30 seconds after circuit 1 to prevent combined transient refrigerant load from exceeding the MOP threshold.
When to call a professional
If MOP alarms persist at normal operating loads with correctly configured threshold and protection parameters, a licensed refrigeration technician should evaluate refrigerant charge, condenser performance, and expansion valve operation. Refrigerant recovery for charge adjustment and pressure switch calibration require EPA 608 or equivalent certification.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.it, www.carel.com