Carel AL57
Driver 2 probe S2 error Circuit 1 off Manual Manual No No AL58 AL59 AL60 Driver
Source: 030221501.pdf
What does Carel AL57 mean?
AL57 signals that Driver 2's S2 probe (suction temperature NTC sensor) has failed or become disconnected. The S2 NTC probe provides the suction temperature reading that Driver 2 uses to calculate superheat. Without it, Driver 2 cannot compute superheat and shuts Circuit 2 off to prevent compressor damage.
Symptoms
- Circuit 2 goes offline immediately upon S2 probe failure.
- AL57 is displayed on the controller and requires manual reset.
- Driver 2 loses its superheat calculation capability.
- Compressors on Circuit 2 stop running.
Common causes
- Broken or disconnected NTC suction temperature probe wiring on Driver 2.
- Failed NTC temperature probe (S2) with open or short circuit.
- Probe installed in incorrect location away from the suction line.
- Corrosion or moisture damage at the S2 probe connector.
- Wiring routed too close to high-voltage cables causing interference.
Diagnostic steps
- 01
Check S2 probe resistance
Disconnect the NTC probe from Driver 2 and measure resistance at the probe leads. At 25°C a standard NTC probe should read approximately 10 kΩ; an open circuit (infinite resistance) or short (near zero) confirms probe failure.
- 02
Inspect probe wiring and connectors
Trace the S2 wiring from probe to Driver 2 input terminal. Look for breaks, pinching against sheet metal, or loose connector pins.
- 03
Verify correct probe installation on suction line
Confirm the NTC is clamped tightly to the insulated suction line downstream of the evaporator and upstream of the expansion valve outlet, with proper insulation over the probe.
- 04
Replace the S2 NTC probe if defective
Install a replacement Carel NTC probe (e.g., NTC006HP0R) and reroute the cable away from power wiring to avoid signal interference.
- 05
Manually reset AL57
After restoring a valid S2 signal, manually reset the alarm from the controller menu. Circuit 2 will restart normal operation.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL57 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
If probe and wiring replacement does not clear AL57, the Driver 2 analog input circuit may be internally damaged. Driver board replacement and refrigerant circuit re-commissioning require certified refrigeration technician skills. Do not operate Circuit 2 without a functioning S2 probe — undetected liquid flooding will damage the compressor.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com