Carel AL61 Error Code
Driver1go-aheadrequest Circuit 1 off No AL62 Driver2go-aheadrequest Driver1 LANd
Source: 030221501.pdf
What does Carel AL61 mean?
AL61 means Driver 1 is requesting a go-ahead signal from the main pCO controller but is not receiving it. The go-ahead request is a LAN-based permission mechanism where the expansion valve driver waits for the master controller to authorize valve operation before starting superheat control. Without the go-ahead, Driver 1 holds Circuit 1 offline.
Symptoms
- Circuit 1 remains offline despite normal operating conditions.
- AL61 displays on the controller and requires manual reset.
- Driver 1 is powered and communicating via pLAN but not regulating.
- No other alarm is active on Driver 1 that would explain the shutdown.
Common causes
- LAN communication interruption between Driver 1 and the pCO master controller.
- Incorrect pLAN address configuration on Driver 1 or the pCO.
- Application software on the pCO not configured to issue go-ahead to Driver 1.
- Driver 1 parameters not matching the expected application program configuration.
- Autosetup procedure not completed on Driver 1 (see AL65).
Ask the AskWhiz AI about Carel AL61
AskWhiz
online
Diagnostic steps
Verify pLAN communication with Driver 1
Check the pLAN network wiring between the pCO controller and Driver 1. Confirm proper termination resistors are in place and no wiring faults exist.
Confirm Driver 1 pLAN address
Navigate to Driver 1's network settings and verify its pLAN address matches what the pCO application program expects. Duplicate addresses on the network will prevent communication.
Check pCO application configuration for Driver 1 go-ahead
Review the pCO application settings to confirm Driver 1 is enabled and the go-ahead output is mapped to the correct network variable.
Complete the autosetup procedure on Driver 1
If AL65 is also active, complete Driver 1's autosetup first. Navigate to the AUTOSETUP menu on the pCO and run the procedure for Driver 1, confirming valve type, refrigerant, and probe configuration.
Manually reset AL61
After resolving the go-ahead condition, manually reset AL61 from the pCO alarm menu.
When to call a professional
If pLAN communication faults persist after wiring and address verification, or if the pCO application software requires reconfiguration or reprogramming, contact a Carel-authorized technician. Application software modifications on pCO controllers should only be performed by personnel with Carel c.strategy training.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com