Carel AL63
AL64 Driver 2 LAN disconnected Circuit 1 off Circuit 2 off Manual Manual Manual
Source: 030221501.pdf
What does Carel AL63 mean?
AL63 means Driver 1 has lost its LAN (pLAN) connection to the pCO master controller. The pLAN network link is required for the master to send superheat setpoints, go-ahead signals, and operating mode commands to Driver 1. When the link drops and does not recover within 30 seconds, Circuit 1 shuts off and AL63 is raised.
Symptoms
- Circuit 1 shuts off after a 30-second LAN communication loss.
- AL63 requires manual reset to recover Circuit 1.
- Other pLAN devices may also show communication errors if the network fault is shared.
- Driver 1 LED may indicate a network error state.
Common causes
- Broken, disconnected, or improperly terminated pLAN wiring between Driver 1 and the pCO.
- Incorrect pLAN network address configured on Driver 1.
- Power supply interruption to Driver 1 during operation.
- Electromagnetic interference disrupting the RS485-based pLAN signal.
- Damaged pLAN card or communication port on the pCO controller.
Diagnostic steps
- 01
Inspect pLAN wiring and termination
Check all RS485 pLAN cable connections between the pCO and Driver 1. Confirm a 120 Ω terminating resistor is installed at both ends of the bus and wiring polarity is correct.
- 02
Verify Driver 1 pLAN address
Confirm Driver 1's pLAN address is set correctly and does not conflict with other devices on the network.
- 03
Measure pLAN signal integrity
Use a multimeter to verify DC bus voltage between pLAN + and − terminals at Driver 1's connector. Check for shorts or opens in the cable run.
- 04
Inspect for EMI sources near the pLAN cable
Ensure the pLAN cable is routed separately from high-voltage power cables. Use shielded twisted-pair cable where possible, grounding shield at one end only.
- 05
Manually reset AL63
After restoring pLAN communication, manually reset AL63. Circuit 1 will resume operation once the go-ahead is re-issued.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel AL63 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
If pLAN communication cannot be restored after wiring inspection and address verification, the pCO communication card or Driver 1 board may have failed. Component replacement on a live controller panel involves high-voltage hazards and requires a licensed technician. Do not run Circuit 1 without pLAN supervision — critical safety commands from the master controller will be lost.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: www.carel.com